Specifications - Omron K8AB-VW Series Quick Start Manual

Single-phase voltage relay
Hide thumbs Also See for K8AB-VW Series:
Table of Contents

Advertisement

K8AB-VW

Specifications

Allowable power supply voltage range
Allowable power supply frequency range
Input frequency range
Overload capacity
Operating value
Setting error
Operating time
Power ON lock time
Operating value
Reset value
Repeat error
Operating time
Power ON lock time
Temperature influence
Humidity influence
Influence of power supply voltage
Influence of power supply frequency
Influence of input frequency
Conforming standards
Applicable
standards
EMC
Safety standards
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Degree of protection
4
85% to 110% of power supply voltage
50/60 Hz ±5 Hz
40 to 500 Hz
Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input
Set value ±10% full scale
Set value ±0.5 s
Operating value ±2%
Error calculation: Error = ((Maximum operating value − Minimum operating value (over 10 operations))/2)/
Average value × 100%
Overvoltage Operating value × 95% ±2%
Undervoltage Operating value × 105% ±2%
Error calculation: Error = ((Maximum reset value − Minimum reset value (over 10 resets))/2)/Average value
× 100%
Operating time repeat error: ±50 ms
Overvoltage:
Measured when input suddenly changes from 0% to 120% of setting.
Undervoltage:
Measured when input suddenly changes from 120% to 0% of setting.
Power ON lock time repeat error: ±0.5 s
(The operating time when the operating time is set to the minimum value and the power supply suddenly
changes from 0% to 100%.)
Operating value
Drift based on measured value at standard temperature:
−20°C to standard temperature: ±1,000 ppm/°C max.
Standard temperature to 60°C : ±1,000 ppm/°C max.
(Humidity: 25% to 80%)
Operating time
Fluctuation based on measured value at standard temperature:
−20°C to standard temperature: ±10% max.
Standard temperature to 60°C : ±10% max.
(Humidity: 25% to 80%)
Operating value
Based on ambient humidity of 65%
25% to 80%: ±5% max.
Operating time
Based on ambient room humidity
25% to 80%: ±10% max.
Operating value: ±5% max.
Operating time: ±10% max.
Note: The error in the operating value and operating time under standard conditions.
Operating value: ±5% max. (at 45 to 65 Hz)
Operating time: ±10% max. (at 45 to 65 Hz)
Note: The error in the operating value and operating time under standard conditions.
At 40 to 500 Hz
Operating value ±5% max.
Operating time ±10% max.
Note: The error in the operating value and operating time under standard conditions.
EN60255-5 and EN60255-6
Installation environment (Pollution Degree 2, Overvoltage Category III)
EN61326
UL508
20 MΩ min.
Between external terminals and case
Between power supply terminals and input terminals (excluding models with DC power supply)
Between power supply terminals and output 1 terminals
Between power supply terminals and output 2 terminals
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
2,000 VAC for one minute
Between external terminals and case
Between power supply terminals and input terminals (excluding models with DC power supply)
Between power supply terminals and output 1 terminals
Between power supply terminals and output 2 terminals
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals
1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s
10 sweeps of 5 min each in X, Y, and Z directions
2
100 m/s
, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward)
Terminal section: Finger protection
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

K8ab-vw1 24 vac/dcK8ab-vw1 100-115 vacK8ab-vw1 200-230 vacK8ab-vw2 24 vac/dcK8ab-vw2 100-115 vacK8ab-vw2 200-230 vac ... Show all

Table of Contents