York ZJ R-410A Technical Manual page 91

R-410a zj/zr/zf series 15 - 25 ton 60 hertz
Table of Contents

Advertisement

ZF180-300 - Hi Static Drive With Powered Convenience Outlet (Continued)
Compressors
Size
Volt
(Tons)
RLA
C1
C2
208-3-60 38.0
42.9
230-3-60 38.0
42.9
300
(25)
460-3-60 18.9
18.5 162.6 130
575-3-60 15.1
15.3 135.9 114
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Motors
(each)
(each)
LRA
MCC
FLA
C1
C2
C1
C2
304
267
59.4
63
4.5
304
267
59.4
62.9
4.3
29.5
29
2.2
23.7
24
1.7
Supply
Pwr
Blower
Conv
Electric Heat Option
Motor
Outlet
FLA
FLA
Model
kW
None
-
E18
13.5
38.6
10.0
E36
27.0
E54
40.6
E72
54.1
None
-
E18
18.0
38.6
10.0
E36
36.0
E54
54.0
E72
72.0
None
-
E18
18.0
19.3
5.0
E36
36.0
E54
54.0
E72
72.0
None
-
E18
18.0
15.4
4.0
E36
36.0
E54
54.0
E72
72.0
251934-YTG-G-0708
Max Fuse
1
MCA
Breaker
(Amps)
Stages
Amps
-
-
155.5
1
37.5
155.5
2
74.9
155.5
2
112.7
201.6
2
150.2
210.9
-
-
155.1
1
43.3
155.1
2
86.6
169.0
2
129.9
190.7
2
173.2
234.0
-
-
73.5
1
21.7
73.5
2
43.3
84.5
2
65.0
95.3
2
86.6
117.0
-
-
59.3
1
17.3
59.3
2
34.6
67.6
2
52.0
76.2
2
69.3
93.5
2
/
3
Size
(Amps)
200
200
200
225
225
200
200
200
225
250
90
90
90
110
125
70
70
70
90
100
91