York ZJ R-410A Technical Manual page 71

R-410a zj/zr/zf series 15 - 25 ton 60 hertz
Table of Contents

Advertisement

ZJ180-300 - Standard Drive Without Powered Convenience Outlet (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA MCC
208-3-60 17.9
120
230-3-60 17.9
120
240
(20)
460-3-60 9.6
70
575-3-60 7.4
53
208-3-60 23.0
160
230-3-60 23.0
160
300
(25)
460-3-60 12.2
87
575-3-60 8.7
62
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
FLA
FLA
FLA
28.0
3.7
15.4
0.0
28.0
3.7
14.4
0.0
15.0
1.9
7.2
0.0
11.5
1.5
5.9
0.0
31.5
3.7
28.0
0.0
31.5
3.7
26.0
0.0
17.1
1.9
13.0
0.0
13.5
1.5
10.3
0.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
E18
13.5
1
37.5
E36
27.0
2
74.9
E54
40.6
2
112.7
E72
54.1
2
150.2
None
-
-
-
E18
18.0
1
43.3
E36
36.0
2
86.6
E54
54.0
2
129.9
E72
72.0
2
173.2
None
-
-
-
E18
18.0
1
21.7
E36
36.0
2
43.3
E54
54.0
2
65.0
E72
72.0
2
86.6
None
-
-
-
E18
18.0
1
17.3
E36
36.0
2
34.6
E54
54.0
2
52.0
E72
72.0
2
69.3
None
-
-
-
E18
13.5
1
37.5
E36
27.0
2
74.9
E54
40.6
2
112.7
E72
54.1
2
150.2
None
-
-
-
E18
18.0
1
43.3
E36
36.0
2
86.6
E54
54.0
2
129.9
E72
72.0
2
173.2
None
-
-
-
E18
18.0
1
21.7
E36
36.0
2
43.3
E54
54.0
2
65.0
E72
72.0
2
86.6
None
-
-
-
E18
18.0
1
17.3
E36
36.0
2
34.6
E54
54.0
2
52.0
E72
72.0
2
69.3
251934-YTG-G-0708
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
106.3
110
106.3
110
112.9
125
160.1
175
169.4
200
105.3
110
105.3
110
126.3
150
147.9
175
191.2
225
55.6
60
55.6
60
63.1
70
74.0
90
95.6
110
43.4
50
43.4
50
50.7
60
59.3
70
76.7
90
141.8
150
141.8
150
141.8
150
175.9
200
185.2
200
139.3
150
139.3
150
140.8
150
162.4
175
205.7
225
72.7
80
72.7
80
72.7
80
81.2
90
102.9
110
53.7
60
53.7
60
56.2
60
64.8
70
82.2
90
71

Hide quick links: