The OptiLogic Control Center uses microprocessor logic to opti- mize operation of the eco HFC-407C Refrigerant for the Global Environment level within LD07431 rooftop unit. LD07430 YORK INTERNATIONAL...
17 Component Static Pressure Drops ... 40 18 Gas Heat Pressure Drops ... 44 19 Electric Heat Pressure Drops ... 46 YORK INTERNATIONAL TABLE OF CONTENTS 20 60 Through 65 Ton Exhaust Fan Data ... 48 21 70 Through 85 Ton Exhaust Fan Data ... 49 22 90 Through 95 Ton Exhaust Fan Data ...
• FlexSys Underfloor Air System Configuration – the eco rooftop is the first packaged rooftop product with designs specifically for use with the YORK Flex- Sys underfloor air system. Ask your local YORK representative for more information. Indoor Air Quality (IAQ) •...
Page 5
OptiLogic continually monitors all control setpoints and configurations. If a unit sensor fails, the con- troller indicates an alarm. If desired, YORK service can provide remote monitoring and automatically schedule a service technician to make the repair and maintain your comfort.
Page 6
STAINLESS STEEL SIDES OF UNIT IAQ DRAIN AND TIE BACKS PAN AND FOR UNIT INTERMEDIATE SERVICING DRAIN PAN ANGLED EVAPORATOR COIL FOR LOWER FACE VELOCITIES RAINHOODS TO PREVENT MOISTURE FROM ENTERING THE UNIT CENTRIFUGAL FAN POWERED EXHAUST 00567VIP YORK INTERNATIONAL...
(IGVs) for duct static pressure control. These con- trol supply duct pressure by modulating dampers (intro- ducing losses and inefficiencies) on the inlet of the fan, open and closed. YORK’s variable frequency drives (VFDs) offer superior fan speed control and quieter, energy efficient operation.
Page 9
In areas where chemicals that can corrode copper are present, such as ammo- nia, YORK recommends that the black fin or Technicoat coating be used for maximum protection. Copper Fin Condenser Coil...
Page 11
7. The high heat option for the YPAL085 provides 900 mbh of heat capacity with an input of 1,125 mbh. This is sufficient for the 875 mbh heating requirement. YORK INTERNATIONAL FORM 100.50-EG3 (802) 8. Determine net cooling and heating capacities if required.
0-33980 0-498 Pa 0-498 Pa 0-498 Pa 1140 4029 5799 4x15 4x10, 2x13 Scroll Scroll 4x25 4x15, 2x20 25-22 28-25 7.5-40 7.5-60 23785-45875 23785-54,367 0-995 Pa 0-995 Pa 15-15 18-18 5-20 10-20 0-33980 0-33980 0-498 Pa 0-498 Pa YORK INTERNATIONAL...
Page 13
Total Filter Face Area (Square Meters) Filters - 5.08cm Carbon (30% Efficient) Quantity Size (Length x Width) (Meters) Total Filter Face Area (Square Meters) Minimum OA Temp. for Mech. Cig. YORK INTERNATIONAL 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced Prop. Prop.
Page 14
Scroll Scroll Scroll 6x16 4x18, 2x15 4x18, 2x15 28-25 28-28 28-28 7.5-60 7.5-60 7.5-60 30582-61164 30582-61164 30582-61164 0-995 Pa 0-995 Pa 0-995 Pa 18-18 18-18 18-18 10-20 10-20 10-20 0-33980 0-33980 0-33980 0-498 Pa 0-498 Pa 0-498 Pa YORK INTERNATIONAL...
Page 15
Total Filter Face Area (Square Meters) Filters - 5.08cm Carbon (30% Efficient) Quantity Size (Length x Width) (Meters) Total Filter Face Area (Square Meters) Minimum OA Temp. for Mech. Cig. YORK INTERNATIONAL 5/4 /enhanced 5/4 /enhanced 5/4 /enhanced Prop. Prop.
29.4°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 50 Ton Model – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 17
25485 29733 31148 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 55 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 19
27184 32706 33980 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 60 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 21
30582 35679 38228 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 65 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 23
30582 35679 38228 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 70 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 25
33980 37378 38228 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 75 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 27
33980 37378 38228 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 80 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 29
30582 37378 45307 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 85 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 31
30582 37378 45307 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 90 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 33
40776 45307 50970 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
CAPACITY (kW) AT ENTERING DRY BULB (°C) 35°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 95 Ton Model – – – – – – – – – – – – – – – – YORK INTERNATIONAL...
Page 35
40776 45307 50970 * Rated performance is at sea level. Cooling capacities are gross cooling capacity. YORK INTERNATIONAL 40.5°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) 46.1°C AIR ON CONDENSER COIL CAPACITY (kW) AT ENTERING DRY BULB (°C) FORM 100.50-EG3 (802)
TABLE 20 – 50 THROUGH 65 TON EXHAUST FAN DATA (CONT’D) TOTAL STATIC PRESSURE (Pascals of water column) m3/hr STD. AIR 13592 20388 27184 1055 11.2 33980 NOTE: * Grey areas indicate operation in motor service factor. 1141 17.7 1161 1025 1072 1104 12.0 1150 12.7 1196 YORK INTERNATIONAL...
TABLE 22 – 90 THROUGH 95 TON EXHAUST FAN DATA (CONT’D) TOTAL STATIC PRESSURE (Pascals of water column) m3/hr STD. AIR 23786 30582 37378 11.7 44174 15.6 16.7 YORK INTERNATIONAL 12.0 14.9 15.7 1034 10.0 13.3 14.4 12.5 13.3 16.7 18.7...
MOP is less than the MCA, then select the lowest standard maximum fuse size greater than or equal to the MCA. Nominal Voltage 400/3/50 24.2 24.2 27.9 27.9 17.9 24.2 17.9 24.2 24.2 24.2 24.2 27.9 24.2 27.9 YORK INTERNATIONAL...
Controls CONTROL SEQUENCES COMMON TO ALL UNITS GENERAL The control system for the YORK eco² Packaged Roof- top Unit is fully self-contained and based around an ™ OptiLogic rooftop unit controller. To aid in unit setup, maintenance, and operation, the OptiLogic controller is equipped with a user interface that is based around a 4 line x 20 character backlit LCD display.
Page 55
This method of economizing allows the reference temperature setting to be set higher than the DB Economizer and is consequently a more effi- cient packaged rooftop economizer. YORK INTERNATIONAL FORM 100.50-EG3 (802) Comparative (Dual) Enthalpy Economizer With the optional comparative enthalpy economizer, the...
Page 56
Outside Air temperature is lower than the Low Ambient Lockout temperature. ™ controller. If the pressure rises to or ™ User Interface. ™ User Interface. ™ controller moni- ™ User controller continuously monitors the YORK INTERNATIONAL ™...
Page 57
This mode is main- tained until the smoke purge input is deactivated and the unit returns to normal operation. YORK INTERNATIONAL Purge When this purge sequence is selected and activated, the Supply Fan is controlled ON and the Exhaust Fan is controlled ON.
Page 58
Ventilation functions (if equipped) will be permit- ted to run with an occupied signal. Economizer func- tions will operate with a “G” call and a call for cooling. ™ Controller will ™ Controller will start the Supply Fan. YORK INTERNATIONAL...
Page 59
OptiLogic controller will modulate the Outside Air damper in addition to staging compressors up and down to maintain the zone temperature setpoint. YORK INTERNATIONAL HEATING OPERATION Thermostat Control If a 7-wire thermostat (2 Cool/2 Heat) controls the unit, all zone temperature setpoint control is maintained at the thermostat.
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIG. 1 – SINGLE-POINT POWER SUPPLY WIRING Electrical / Controls Box Power Side Control Side Wiring Terminal Block LD06414 YORK INTERNATIONAL...
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIG. 2 – SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT YORK INTERNATIONAL Electrical / Controls Box Power Side...
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIG. 3 – DUAL-POINT POWER SUPPLY WIRING Electrical / Controls Box Power Side Control Side Wiring Terminal Block LD06416 YORK INTERNATIONAL...
FIG. 5 – GENERAL ARRANGEMENT DRAWING – 50-65 TON MODEL TOP VIEW LEFT SIDE VIEW 49.69 91.44 24.61 485.14 209.87 179.38 11.75 233.68 3.97 50-65 Ton Models 3.175 FPT COUPLING DRAIN CONNECTION FRONT 600.7 973.30 873.76 369.89 210.18 11.75 90.33 11.75 YORK INTERNATIONAL LD07880 270.83...
4. Bottom supply available on all configurations. 5. Rear return not available with exhaust/relief options. 6. Center of gravity information is based on a base cooling only unit. FIG. 6 – GENERAL ARRANGEMENT DRAWING – 70-95 TON MODEL YORK INTERNATIONAL TOP VIEW 3.175 FPT COUPLING...
5. Rear return not available with exhaust/relief options. 6. Rear return not available with exhaust/relief options. 7. Center of gravity information is based on a base cooling only unit. FIG. 8 – GENERAL ARRANGEMENT DRAWING – 70-95 TON MODEL YORK INTERNATIONAL TOP VIEW 3.175 FPT COUPLING...
1. Left side shown, RH side available (mirror image). TABLE 33 – OPTIONAL SIDE RETURN (CM) MODEL 70-85 157.80 147.32 90-95 174.62 164.14 105.73 FIG. 9 – GENERAL ARRANGEMENT DRAWING – 70-95 TON MODEL (ONLY) 101.6 128.91 131.13 – 70-95 Ton Models (ONLY) LD07313 YORK INTERNATIONAL...
YORK INTERNATIONAL FORM 100.50-EG3 (802) Casing The unit cabinet shall be one-inch double-wall construc-...
Page 72
Polyurethane sleeves shall protect all small diameter distributor tubing to the evaporator coil to prevent the tubes from copper-to-copper contact during shipment or operation. YORK INTERNATIONAL...
Page 73
The heater shall be an industrial grade design using an open coil(s) made of the highest grade resistance wire YORK INTERNATIONAL FORM 100.50-EG3 (802) containing 80% nickel and 20% chromium. The resis- tance coil(s) shall be adequately supported in the air stream using ceramic bushings in the supporting frame- work.
Page 74
Wall-Mount Zone Sensor, Nonscaled Setpoint Ad- justment – a 1 kOhm thin-film nickel zone sensor for wall mounting. This zone sensor is for sensing tem- perature and includes a non-scaled (warmer-cooler) set- point adjustment feature. YORK INTERNATIONAL...
Page 75
Barometric Relief – building air exhaust shall be ac- complished through barometric relief dampers installed in the return air plenum. The dampers will open relative YORK INTERNATIONAL FORM 100.50-EG3 (802) to the building pressure. The opening pressure shall be adjustable.