Exhaust Fan Data

EXHAUST FAN MOTOR SIZING INSTRUCTIONS
In order to determine the proper exhaust fan motor size, add the return duct static pressure to the appropriate damper
pressure drop value in Table 14 to get the total static pressure applied to the exhaust fan. Based on the exhaust fan
airfl ow and total static pressure, determine the brake horsepower and RPM of the exhaust fan.
TABLE 15 – FORWARD-CURVED FAN
CFM STD.
0.3
AIR
BHP
6000
8000
10000
12000
14000
16000
5
18000
6.8
20000
9.1
22000
11.8
24000
15.1
26000
18.9
NOTE: For performance at operating points not included in these tables, consult your local YORK representative.
JOHNSON CONTROLS
Total Static Pressure (inches of water column)
0.5
RPM
BHP
528
5.7
579
7.7
632
10.1
685
13
739
16.4
794
0.8
RPM
BHP
584
6.4
632
8.5
681
11.1
731
14.1
782
17.6
FORM 100.50-EG5 (108)
1
RPM
BHP
5.4
633
7.2
678
9.3
725
12
772
15.1
821
18.8
RPM
645
680
721
765
811
858
25