343615-YTG-B-0308
TABLE 24: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/ POWERED CONVENIENCE OUTLET (CONT)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 28.8 145.0 45.0
230-1-60 28.8 145.0 45.0
208-3-60 17.3 123.0 27.0
060
(5.0)
230-3-60 17.3 123.0 27.0
460-3-60 9.6
70.0
575-3-60 7.4
53.0
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
2.3
7.6
10.0
2.3
7.6
10.0
2.3
7.6
10.0
2.3
7.6
10.0
15.0
1.3
7.6
5.0
11.5
1.3
7.6
4.0
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
E05
4.0
1
19.2
E07
5.6
1
26.9
E10
8.0
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
E30
22.2
2
106.7
None
-
-
-
E05
5.3
1
23.0
E07
7.5
1
32.6
E10
10.6
1
46.1
E15
15.9
2
69.1
E20
21.2
2
92.2
E30
29.6
2
128.7
None
-
-
-
E05
4.0
1
11.1
E07
5.6
1
15.5
E10
8.0
1
22.2
E15
11.9
2
33.0
E20
15.9
2
44.1
E30
22.2
2
61.6
None
-
-
-
E05
5.3
1
13.3
E07
7.5
1
18.8
E10
10.6
1
26.6
E15
15.9
2
39.9
E20
21.2
2
53.2
E30
29.6
2
74.3
None
-
-
-
E07
6.8
1
8.5
E10
10.1
1
12.7
E15
13.6
2
17.1
E20
19.5
2
24.5
E30
28.8
2
36.1
None
-
-
-
E10
10.6
1
10.6
E15
15.9
1
16.0
E20
21.2
2
21.3
E30
30.4
2
30.5
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
55.9
60
55.9
60
55.9
60
70.1
80
93.5
100
117.6
125
155.4
175
55.9
60
55.9
60
61.1
70
77.2
80
104.8
110
132.4
150
176.2
200
41.5
45
41.5
45
41.5
45
49.8
50
63.3
70
77.2
80
99.0
100
41.5
45
41.5
45
44.6
45
53.9
60
69.8
70
85.7
90
111.0
125
22.1
25
22.1
25
26.2
25
31.4
30
40.3
40
54.3
60
17.3
20
21.5
20
27.9
30
34.3
35
45.4
45
23