Appendix C : Port Configurations

RS232/RS485 interface
- Modbus RTU
- 9600 baud, 8 data bits, no parity, 1 stop bit
Network interface
- Modbus/TCP
- TCP port 502
- 10base-T half-duplex
- Auto-negotiation not supported
Modbus Functions accepted
- Fn 1
Read Coils
- Fn 3
Read Holding Registers
- Fn 5
Write Single Coil
- Fn 6
Write Single Register
- Fn 16
Write Multiple Registers
17

Appendix D : Global Parameters

Global Parameter
Description
Mnet Comms Status
Provides an indication of the communication status
between the G-50 and the Mitsubishi M-Net network.
00 :
01 :
Note: While M-Net is initialising, the air-conditioning is
effectively offline to control and monitoring
requests.
G50 Comms Status
Provides an indication of the communication status
between the Procon MOD-IP/50 and the G-50.
00 :
01 :
Note: 'G-50 not responding' either means the G-50 is
switched off or is not connected to the network.
Global Forced Off
Enables and disables the Global Forced-Off command.
This setting allows the BMS to provide functionality
equivalent to the 'Enable Link' described in section 2.3
M-Net Initialising
M-Net OK
G-50 not responding
G-50 comms OK
18