3. DRY OPERATION
The compressor frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 5.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
64rps (07/09 type), 61rps (12/14 type), for a minute.
( Table 5 : Compressor frequency in Dry mode)
Model
X zone
07/09
J zone
Y zone
( Fig.2 : Compressor control based on room temperature )
Roomtemperature drops
X zone
Ts+0.5°C
J zone
Ts -1.5°C
Y zone
Operating
Model
frequency
37rps
12/14
28rps
0rps
Roomtemperature rises
Ts+1.5°C
Ts -0.5°C
Operating
frequency
X zone
33rps
J zone
25rps
Y zone
0rps
01-03