Menu Options

LED Display
Enable or disable inverter boost operation. (compressor speed may
St
increase when this feature is on) (inverter only)
Boost mode will operate above this selected temperature. On =
tt
boost mode always on (default = 105°F) (inverter only)
CAP
Cooling Airflow Profile setting (default = profile D shown as 4)
Heat Pump compressor lockout temperature. Furnace will act as
CP
primary heat source below this temperature. (Default = 45°F)
Compressor off delay at the beginning and end of a defrost cycle.
CdL
(default = 30 seconds)
CFd
Cooling Airflow Off Delay Time. (default = 60 seconds)
CL
Resets all cooling settings to factory default.
Cnd
Cooling Airflow On Delay Time (default = 5 seconds)
C
Control Firmware Revision Number
Enable or disable inverter charge mode.
C
Select the range that includes the desired compressor RPS for
CP
inverter cooling operation. See inverter manual for menu options
Maximum Compressor RPS for cooling mode. (inverter only)
CS
Percentage of high stage cooling airflow to run during low stage
CSt
operation. (default = 70%)
Cooling Airflow Trim (default 0%)
CtF
High Cooling Airflow Trim for inverter units. See inverter manual for
CtH
menu options and defaults
Intermediate Cooling Airflow Trim for inverter units. See inverter
CtI
manual for menu options and defaults
Low Cooling Airflow Trim for inverter units. See inverter manual for
CtL
menu options and defaults
Compressor run time between defrost cycles. (default = 30
dFI
minutes) (2 stage units)
Enables or disables dehumidification feature in the outdoor unit.
dHE
(default = Enabled)
Select "1" to enable dehumidification when the thermostat DH
dHL
terminal is energized. Select "0" to enable dehumidification when
the thermostat DH terminal is de-energized. (default = 1)
Gas heat operation during defrost. 1 = low heat, 2 (default) = high
dHS
heat
View 6 most recent fault codes and Clear Fault Codes if desired
FCL
(outdoor communicating units)
Force system into a defrost cycle (inverter units)
FdF
Constant Fan Speed as percent of maximum airflow. Default =
FSd
25%
Gas Heat Airflow (percentage of maximum system airflow)
AF
Fd
Gas Heat Fan Off Delay (default = 90 seconds)
Gas Heat Fan On Delay (default = 30 seconds)
nd
Enables gas heat at 100% for pressure testing during
Pt
commissioning.
Percentage of high stage gas heating airflow to run during low
St
stage gas heat operation. (default = 70%)
Menu Description
LED Display
tF
Gas Heat Airflow Trim (default = 0%)
Maximum Compressor Run Time Between Defrost Cycles (default
HdI
= 120 minutes)
HFd
Heat Pump Heating Airflow Off Delay Time (default = 60 seconds)
Heat Pump Heating Airflow On Delay Time (default = 5 seconds)
Hnd
Select the range that includes the desired compressor RPS for
HP
inverter heating operation. See inverter manual for menu options
HS
Maximum Compressor RPS for Heating Mode (inverter only)
Ht
Reset all heat pump heating settings to factory default.
Percentage of high stage heat pump heating airflow to run during
HSt
low stage operation. (default = 70%)
Heat Pump Indoor Airflow Trim (default = 0%)
HtF
High Heating Airflow Trim for Inverter Units. See inverter manual for
HtH
menu options and defaults
Intermediate Heating Airflow Trim for Inverter Units. See inverter
HtI
manual for menu options and defaults
Low Heating Airflow Trim for Inverter Units. See inverter manual for
HtL
menu options and defaults
View 6 most recent fault codes and clear all fault codes if desired.
LF
(furnace)
Restart communications between the indoor and outdoor unit.
Ln
Select the number of stages for the non-communicating outdoor
DS
unit. Default = OFF meaning no outdoor unit.
Enable Pump Down Mode
PPd
Resets furnace settings to factory defaults.
Fd
Maximum Current Option (system will limit capacity to percentage
SCt
of maximum current) (default = 100%)
Control Shared Data Revision Number
S
St
Resets all outdoor unit settings to factory defaults.
System Verification Test (inverters only)
St
Indoor Airflow for non-communicating outdoor units. (values based
tn
on 400CFM per ton) (default = 3.0 Ton)
Select Outdoor Unit Elevation (SL=same level, OL = outdoor lower,
t
IL = indoor lower) Default = Outdoor Lower
1 = system will try to satisfy the thermostat quickly.
CFS
5 (default) = system will try to satisfy the thermostat more slowly.
Menu is enabled if the CFS menu is set to 6. Select the target time
tt
the system will attempt to satisfy the thermostat.
Menu is enabled if the CFS menu is set to 6. Select the percentage
SUP
past the target time when the system will transition to gas furnace
operation during heat mode.
Menu is enabled if the CFS is set to 6. (the gas furnace will run
during the next heat call if the heat pump fails to satisfy the
tt
custom target time for this number of consecutive cycles) (default
= 20 cycles)
Menu is enabled if the CFS menu is set to 6. (if low stage gas heat
is able to consecutively satisfy the thermostat under the set target
Utt
time for this number of cycles, the system will transition to the
heat pump for primary heating)
Menu is enabled if the CFS menu is set to 6. (this percentage will
help determine when switching back to heat pump operation is
SdP
appropriate. Default = 20%. If target time = 20 minutes, low stage
furnace operation must satisfy the thermostat by less than 16
minutes. (target time - 20% default = 16 minutes).
44