Siemens SIMATIC S7-1500 Function Manual page 49

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Communications services
3.6 Secure Communication
Procedure
STEP 7 automatically loads the required CA certificates together with the hardware
configuration to the participating CPUs so that the requirements for certificate verification
exist for both CPUs. You therefore only have to generate the device certificates for the
respective CPU; STEP 7 does the rest for you.
1. Mark PLC_1 and activate the "Use global security settings for certificate manager" option
in the "Protection & Security" section.
2. Log in as a user in the project tree in the "Global security settings" section. For a new
project, the "Administrator" role is planned for the first login.
3. Return to the PLC-1 in the "Protection & Security" section. Click in an empty line in the
"Certificate subject" column in the "Device certificates" table to add a new certificate.
4. In the drop-down list for selecting a certificate click the "Add" button.
The "Create Certificate" dialog opens.
5. Leave the default settings in this dialog. They are tailored to the usage of Secure Open
User Communication (usage: TLS).
Tip: Supplement the default name of the certificate subject, in this case the CPU name. In
order to differentiate you better leave the default CPU name in case you have to manage
a large number of device certificates.
Example: PLC_1/TLS becomes PLC_1-SecOUC-Chassis17FactoryState.
6. Compile the configuration.
The device certificate and the CA certificate are part of the configuration.
7. Repeat the steps described above for PLC_2.
In the next step you have to create the user programs for the data exchange and load the
configurations together with the program.