OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
Node classes
OPC UA servers provide information in the form of nodes. A node can be, for example, an
object, a tag, a method or a property.
The example below shows the address space of the OPC UA server of an S7-1500 CPU
(extract from the OPC UA client "UaExpert" from Unified Automation).
Figure 9-7
In the figure above, the "MyValue" tag is selected (highlighted in gray).
This tag is located below the "Memory" node, which has the node class "Object".
"Memory" is below the "PLC_1" node (also an Object).
Address space
The nodes are linked over references, for example, the reference "HasComponent, which
represents a hierarchical relationship between a node and its subordinate nodes. With their
references, the nodes form a network that can, for example, take the form of a tree.
A network of nodes is also called an address space. Starting from the root, all nodes can be
reached in the address space.
160
Example of the address space of the OPC UA server of an S7-1500 CPU
Function Manual, 11/2019, A5E03735815-AH