p0144[0...n]
Sensor Module detection via LED / SM detection LED

SERVO, VECTOR

Can be changed: U, T
Data type: Unsigned8
P-Group: Encoder
Not for motor type: -

Min

0

Description:

Detects the Sensor Module assigned to this drive and data set.
Note:
While p0144 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Sensor Module.
p0145[0...n]
Voltage Sensing Module, activate/de-activate / VSM act/deact
A_INF, S_INF
Can be changed: C1(4), T
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/de-activate a Voltage Sensing Module (VSM).
Values:
0:
1:
2:
Recommend.:
After inserting a component, before activating, first wait for Alarm A01317.

Dependency:

Refer to: r0146
Refer to: A01317
Note:
For chassis infeeds, it is not possible to activate/de-activate the Voltage Sensing Module (VSM) via p0145. The
VSM can only be activated/de-activated in the group with the appropriate infeed via p0125[0...n].
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
p0145[0...n]
Activate/de-activate encoder interface / Enc_intf act/deact
SERVO, VECTOR
Can be changed: C1(4), U, T
Data type: Integer16
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Setting to activate/de-activate an encoder interface (Sensor Module).
Values:
0:
1:
2:
Recommend.:
After inserting a component, before activating, first wait for Alarm A01317.
Dependency:
Refer to: r0146
Refer to: A01317
Note:
The de-activation of an encoder interface corresponds to the"parking encoder" function and has the same effect.
The activation of a component can be rejected if the component was inserted for the first time.
In this case, it is only possible to activate the component when the pulses for all of the drive objects are inhibited.
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
De-activate component
Activate component
Component, de-activate and not present
De-activate component
Activate component
Component, de-activate and not present

Calculated: -

Dynamic index: EDS, p0140
Units group: -

Max

1
Calculated: -
Dynamic index: p0140
Units group: -
Max
2
Calculated: -
Dynamic index: EDS, p0140
Units group: -
Max
2
Parameters
List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
1-101