Setup Menu Map - Xantrex 120 VAC/60 Owner's Manual

Sw series inverter/chargers
Table of Contents

Advertisement

SETUP MENU MAP

The SETUP MENU provides all the controls and settings needed when installing or adjusting the
system. To access the SETUP MENU, press both the red ON/OFF MENU and green GEN MENU buttons
on the Control Panel at the same time. To exit the SETUP MENU, press the red ON/OFF MENU button or
press the down MENU HEADING button until you reach the USER MENU (menu headings 1-8).
Inverter Setup
9
Set Grid Usage
FLT SELL SLT LBX
Set Low battery
cut out VDC
11.0
Set LBCO delay
minutes
10
Set Low battery
cut in VDC
13.0
Set High battery
cut out VDC
16.0
Set search
watts
48
Set search
spacing
59
Bulk Charge
Trigger Timer
15
Set Start Bulk
time
00:00
To disable timer
set to 00:00
If grid timer
active set bulk
time after start
charge time.
In SLT mode don't
disable this
timer. It is the
daily chg time.
2001 Xantrex Technology, Inc.
5916 - 195th Street N. E.
Arlington, WA 98223
MENU HEADINGS
Battery Charging
AC Inputs
10
Set Bulk
Set Grid (AC1)
volts DC
14.4
amps AC
Set Absorption
Set Gen (AC2)
time h:m
02:00
amps AC
Set Float
Set Input lower
volts DC
13.4
limit VAC
Set Equalize
Set Input upper
volts DC
14.4
limit VAC
Set Equalize
time h:m
02:00
Set Max Charge
amps AC
20
Set Temp Comp
LeadAcid
NiCad
Low Battery
Battery Selling
Transfer (LBX) 16
Set Low Battery
Set Battery Sell
TransferVDC
11.3
volts DC
Set Low battery
Set Max Sell
cut in
VDC
13.0
amps AC
See menu 9 to
See menu 9 to
enable LBX mode.
enable SELL mode.
Make sure LBX is
Make sure LBX is
above LBCO volts.
above LBCO volts.
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
Gen Auto Start
Gen starting
11
setup
12
details
Set Load Start
Set RY7 Function
60
amp AC
20
GlowStop
Set Load Start
Set Gen warmup
30
delay min
5.0
seconds
Set Load Stop
Set Pre Crank
108
delay min
5.0
seconds
Set 24 hr start
Set Max Cranking
132
volts DC
12.3
seconds
Set 2 hr start
Set Post Crank
volts DC
11.8
seconds
Set 15 min start
volts DC
11.3
Read LBCO 30 sec
start VDC
11.0
Set Exercise
period days
30
Set Maximum run
time h:m
08:00
Set Max Run time
to 0 to defeat.
Set Exercise to 0
to defeat.
See menu 9 to
to set LBCO.
Grid Usage Timer
Information file
17
18
battery
Start Charge
Batt temp comp
13.4
time
21:00
changes battery
End Charge
voltage reading
30
time
21:00
away from actual
After Start
HBCO resets at:
Charge time:
6v/48, 3v/24 and
SELL mode
1.5v/12v under
charges battery.
HBCO.
FLT mode
LowBattTransfer
charges battery
used in LBX, FLT
After End Charge
Modes only. Goes
time:
back to battery
SELL mode sells
at LowBattCutIn
battery to AC1.
(aka LBCI).
FLT mode drops
For LBX mode set
AC1 and inverts
below LBCI so
Timer on when
charger won't
start < > end;
cycle batteries
timer off when
up and down and
start = end
set LBCO below.
Sell and float
modes use timer
SLT and LBX mode
ignore timer
SW Series Inverter/Charger
Rev. C: February 2001
MENU SYSTEM
Auxiliary Relays
13
R9 R10 R11
14
Set Relay 9
Run
volts DC
14.5
R9 Hysteresis
60
volts DC
01.0
Set Relay 10
10
volts DC
14.8
R10 Hysteresis
10
volts DC
01.0
Set Relay 11
30
volts DC
15.0
R11 Hysteresis
volts DC
01.0
Close on batt >
setpoint.
Open on batt <
setpoint - Hys
Relays have 2
second delay on
Close, 0.1 sec
delay on open
End Setup Menu
19
20
Page
Part No. 2031-5