Overcrank Shutdown; Rpm Sensor Loss Shutdown; Low Fuel Pressure Warning; Dc Fuses - Generac Power Systems 0065781 Owner's Manual

Stationary industrial generators standalone gas
Table of Contents

Advertisement

General Information
2.3.5— Overcrank Shutdown
After a pre-specified duration of cranking, this function ends the cranking if the engine has failed to start. The default
settings are:
The unit will attempt to start (crank) three times.
Each crank cycle lasts either 10 or 15 seconds, followed by a five second rest (to cool the starter).
After three starting attempts the unit will shutdown.
2.3.6— RPM Sensor Loss Shutdown
If the speed signal to the control panel is lost, engine shutdown will occur.
2.3.7— Low Fuel Pressure Warning
Some gaseous units are equipped with a low fuel pressure warning switch which will trigger a Warning alarm if
the fuel pressure drops below a minimum setting.
Diesel units with fuel tanks are equipped with High and Low fuel level warning alarms, as well as a low fuel level
shutdown alarm.
2.4 — DC Fuses
Located inside the front panel, the fuses protect the control panel wiring and components from damaging overload. For
fuse location and identification, see Figure 3-4.
2.5 — Fuel System
This generator set is equipped with one of the following fuel systems:

Diesel fuel system

Natural Gas (NG) fuel system
LP gas vapor withdrawal fuel system (LPV)
LP gas liquid withdrawal fuel system (LPL)
Dual fuel system: Natural Gas (primary fuel source), LP gas vapor (secondary fuel source)
Dual fuel system: Natural Gas (primary fuel source, LP gas liquid (secondary fuel source)
2.5.1— Diesel Fuel System
The manufacturer recommends the use of No. 2 diesel fuel when temperatures are above freezing, and No. 1 diesel
fuel when temperatures drop below freezing. Diesel fuel must meet the following requirements:
Beginning October 1, 2010, owners and operators that use diesel fuel must use diesel fuel that meets:
Sulfur content of 15 parts per million (ppm) maximum.
Cetane index or aromatic content as follows: A minimum cetane index of 40, or a maximum aromatic content of
35 volume percent.
2.5.2— Natural Gas Fuel System
Natural gas is supplied by a local utility in its vapor state through in ground piping.
2.5.3— LP Fuel System
LP is supplied as a liquid in pressurized tanks. It is usually made up of propane, butane, or a mixture of both gases.
8
Owner's Manual for Stationary Industrial Generators