Advertisement

Technical data

Power loss of the Power Modules
Note
Power loss for the FSA ... FSC Power Modules
The values specified for the power loss are typical values at 100% of the rated speed and
100% of the load corresponding to Low Overload.
Power loss for the FSD ... FSG Power Modules
The values specified for the power loss are typical values at 90% of the rated speed and
100% of the load corresponding to Low Overload.
Protective devices for the Power Module
The fuses listed in the following tables are examples of suitable fuses.
Additional components for branch protection are available in the Internet:
(https://support.industry.siemens.com/cs/ww/en/view/109486009)
Number of starting operations for converter
The frequency of operation for the converter is every
120 s.
The number of starting operations states how often line
voltage may be switched to the de-energized converter.
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
Branch protection and short-circuit strength according to UL and IEC
6
73