Data in the PROFIBUS-DP messages
1.5.4 CFC-Incoming annunciations
References
1.5.5 Error with a summary alarm
References
1-12
The CFC-Incoming annunciations allow routing of further protection
annunciations on PROFIBUS-DP, which are not contained in the
standard mapping (e.g. ">BLK 50/51", internal object number = 1704 or
">BLK 50N/51N", internal object number = 1714).
You find information about this in the manual "7SJ61...63, 7SJ65,
6MD63, 7UM61 PROFIBUS-DP - Communication profile" (ref. to page i)
in
the
chapter
"PROFIBUS-DP
Customization of the allocations".
Standard mapping 2-1: ref. to chap. 2.1.4
Standard mapping 2-2: ref. to chap. 3.1.4
Standard mapping 2-3: ref. to chap. 4.1.4
Standard mapping 2-4: ref. to chap. 5.1.4
The "Error with a summary alarm" is ON if at least one of the following
internal alarms assumes the value ON.
Depending on the device composition not all alarms are available.
7SJ61, 7SJ62:
•
The "Error with a summary alarm" corresponds to the internal alarm
"I/O-Board error".
•
Additionally with firmware version 4.3 or higher: "Error Board 1",
"Error 5V", "Error 1A/5A wrong", "Error neutral CT", "Error: Range
CT Phase wrong"
7SJ63, 7SJ65, 6MD63:
•
"Error Board 1", "Error Board 2", "Error Board 3", "Error Board 4",
"Error Board 5", "Error Board 6", "Error Board 7", "I/O-Board error",
"Error 5V", "Error 0V", "Error -5V".
•
Additionally with firmware version 4.3 or higher: "Error Power
Supply", "Error 1A/5A wrong", "Error neutral CT", "Error: Range CT
Phase wrong"
Standard mapping 2-1: ref. to chap. 2.2.1.5
Standard mapping 2-2: ref. to chap. 3.2.1.5
Standard mapping 2-3: ref. to chap. 4.2.1.5
Standard mapping 2-4: ref. to chap. 5.2.1.8
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
–
Parametrization
in
C53000-L1840-B006-02
DIGSI,