Chapter 2 Installation And Wiring - Mitsubishi Electric 800 Series Instruction Manual

Functional safety, compact, high functionality inverters
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2
Installation and Wiring
CAUTION
• Ensure the safety programmable controller and the inverter are mounted closely in an enclosure meeting IP54 and all interconnection
wiring is short and protected against open and short circuit faults. For details, refer to ISO/IEC 13849-2.
 Installation
Safety sub-functions of the Mitsubishi Electric FR-E800-SCE inverter should be used under the following conditions and
environment.
Item
Surrounding air temperature
Ambient humidity
Storage temperature
Vibration
Altitude
Atmosphere
Overvoltage category
Pollution degree
Installation
*1
Derate the rated current when using the inverter in a temperature of 50°C or higher.
*2
Temperature applicable for a short time, for example, in transit.
*3
For installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
WARNING
• To avoid an electric shock hazard, install a magnetic contactor (MC) at the input side of the inverter.
• Before wiring or inspection of the inverter, open the contact of MC to switch OFF the power and check that the display of the operation
panel is OFF. Any person who is involved in wiring or inspection shall wait for 10 minutes or longer after power OFF and check the
voltage on the bus capacitors (between terminals P/+ and N/-) using a digital multimeter or other tester. The capacitor is charged with
high voltage for some time after power OFF, and it is dangerous.
10
2. Installation and Wiring
-20°C to +60°C (non-freezing)
With circuit board coating (conforming to IEC 60721-3-3 3C2): 95% RH or less (non-condensing),
without circuit board coating: 90% RH or less (non-condensing)
*2
-40°C to +70°C
2
5.9 m/s
or less at 10 to 55 Hz (in either X, Y, or Z direction)
200/400 V class: Maximum 3000 m. 600 V class: Maximum 2000 m.
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
III or lower
II or lower
Vertical installation in the enclosure
Condition
*1
*3