White Rodgers 1F95-0680 Installation And Operating Instructions Manual page 6

Blue commercial non-programmable thermostat with automatic heat/cool changeover option and damper control
Table of Contents

Advertisement

INSTALLER/CONFIGURATION MENU
21
20 18
MENU
22
21 19
MENU
MENU
23
22 20
MENU
24
23 21
MENU
25
24
MENU
MENU
MENU
26
25
MENU
27
26 22
MENU
28
27 23
MENU
29
28 24
MENU
MENU
30
29 25
MENU
MENU
31
30 26
MENU
32
31 27
MENU
1) This control can be confi gured for:
MS 2 – Multi-Stage System (no heat pump)
HP 1 – Heat Pump with one stage of compressor
HP 2 – Heat Pump with two stage compressor or two
compressor system, Gas or Electric backup
SS 1 – Single Stage System
2) GAS or Electric (ELE) fan operation. If the heating system
requires the thermostat to energize the fan, select ELE.
Select GAS if the heating system energizes the fan on a
call for heat.
3) Select Cool Savings™ value – Selects the amount of
adjustment for the Cool Savings™ feature in Cool mode
with 1 (1°) being the least amount of adjustment and 6
(6°) being the most amount of adjustment. Default value
is 3. Cool Savings is an optional energy saving feature that
can reduce your cooling costs. It is based on the principal
that lower indoor humidity makes a slightly higher tem-
perature feel more comfortable. Cool Savings operates
during periods of high demand which normally occur on
the hottest summer days when a cooling system may run
for hours to reach the thermostat setting. Long cooling
run times also lower the indoor humidity. Cool Savings,
6
dS (On)
(OFF)
Keypad Lockout
(000)
Keypad Lockout
L Heat
(99)
L Cool
(45)
CO
(05)
(dF)
cd
(60)
AO
(80)
(OFF) EC
(O) pp
Change Filter (OFF)
Change Filter (200 h)
(OFF)
Change UV Lamp
(350)
Change UV Lamp
Cool On (o)
RUN SCHED
Off
Selects Automatic Daylight Saving Time option
L, P, Limit
Selects one of 3 Keypad Lockout confi gurations
Limit - Limited Temperature RANGE
1-999
Selects personal lockout code. 000 is NOT A
L 62 to L 98
L 46 to L 82
6-50
Selects outdoor Compressor OFF temperature
(Balance Point temperature). 05 disables fea-
EA
Selects between dF (dual Fuel) or EA (Electric
Selects Compressor delay OFF time in seconds
Selects AO (Auxiliary OFF) temperature. Fea-
ture disabled is 80 selected. Outdoor Remote
On
1-3
Selects no. of hours of preoccupancy purge time
(hours the Fan runs (C an A1 energized)
On
Selects Filter Change-out Indicator On or OFF.
25-1975 h
Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
On
25-1975
Selects no. of Days between changing UV Lamp
Heat On (b)
Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal
very slowly, adjusts the setpoint temperature to make the
setpoint closer to the displayed room temperature, to a
maximum of the number of degrees you select. Adjust-
ing the setpoint temperature over a long cooling run time
allows the system to reach your set temperature and turn
off. The room temperature will actually be higher than the
thermostat displays but the reduction in humidity will allow
comfort at the slightly higher temperature.
To turn this feature on in the Cool mode press Cool
Savings. The display will show "Save" next to the set-
point temperature. When Cool Savings is making adjust-
ments to the room temperature display "Save" will be
fl ashing and the displayed room temperature may vary
within the adjustment range you selected.
If "Save" is not displayed and this feature is OFF, no
change will occur when the cooling system is continuously
running during periods of high demand.
4) Energy Management Recovery: (this step is skipped if
confi gured to be non-programmable).
Energy Management Recovery (E) On enables the ther-
mostat to start heating or cooling early to make the building
temperature reach the program setpoint at the time you
L - Total Keypad Lockout
P - Partial Keypad Lockout
(Up and Keys still work)
VALID CODE.
Select's Limited HEAT Range
Select's Limited COOL Range
ture. Outdoor Remote required
Aux) only available is CO > 6
required
Selects Economizer On/OFF
prior to occupied period)
Selects UV Lamp
Timer: On/OFF
Returns to Normal Operation