106 Technical data
Input power (DC) connection
Voltage (U
)
1
Input terminals
Resistor connection
Voltage (U
)
2
Maximum resistor cable
length
Terminals (outgoing)
Terminals (incoming)
Efficiency
Efficiency
Degree of protection
Degree of protection
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Altitude above sea level
ACS880-104-xxxx-3 modules: 513...566 V DC. This is indicated in the type desig-
nation label as typical input voltage level 566 V DC.
ACS880-104-xxxx-5 modules: 513...707 V DC. This is indicated in the type desig-
nation label as typical input voltage levels 566 / 679 / 707 V DC.
ACS880-104-xxxx-7 modules: 709...976 V DC. This is indicated in the type desig-
nation label as typical input voltage levels 742 / 849 / 976 (849 UL, CSA) V DC.
M12, maximum intrusion into module 20 mm (0.8").
0...U
3-phase symmetrical.
1
For ACS880-104-xxxx-3 modules: This is indicated in the type designation label
as typical output voltage level 3x 0...566 VDC.
For ACS880-104-xxxx-5 modules: This is indicated in the type designation label
as typical output voltage levels 3x 0...566 / 679 / 707 VDC.
For ACS880-104-xxxx-7 modules: This is indicated in the type designation label
as typical output voltage levels 3x 0...742 / 849 / 976 (849 UL, CSA) VDC.
300 m (984 ft)
Busbars to quick connector: M12. Torque: 50 N·m (37 lbf·ft)
Busbars to support insulators: M8. Torque: 9 N·m (6.5 lbf·ft)
Cables to busbars: M12. Torque: 70 N·m (52 lbf·ft)
Cables to busbars: M12. Torque: 70 N·m (52 lbf·ft)
Approximately 98% at nominal power level
IP00
Operation installed for
stationary use
0...4000 m (13123 ft)*
Output derated above 1000
m (3281 ft). See section
Altitude derating.
*Neutral-grounded TN and
TT network systems, non-
corner-grounded IT net-
work systems. Corner-
grounded TN, TT and IT
network systems up to 600
V.
Storage in protective
package
-
Transportation in protect-
ive package
-