4.2
Meter run characteristics 
Standards used as a basis 
Conditions for the meter 
run 
User manual for HON R100 gas pressure regulator with HON P095NG pilot 
No. 
Meaning 
11 
Vent line 
12 
Relief line 
13 
Blowdown line 
 
Following is the meaning of the acronyms: 
Acr. 
Meaning 
DN 
Nominal size of pipe 
L
 
Undisturbed length of pipe 
uR
* Shut‐off device with undisturbed flow pattern (ball valve) can be incorporated 
 
The following recommendations are based on the measuring line connection conditions set 
forth in standards (DIN) EN 334 and (DIN) EN 14382. The company operating the system is 
the sole party responsible for the meter run working properly. 
 
 A pipe area with a steady flow pattern must be selected for the sensing point. There 
must not be any components that disturb the flow directly upstream and downstream 
of the sensing point, e.g., orifice plates, expanders, bends, junctions, shut‐off devices, 
etc. 
 The flow rate at the sensing point should not exceed approx. 25 m/s, depending on the 
system conditions. 
 In the case of specific system circuits (such as gas regulating lines for gas engines) and in 
the case of gas burners, flow rates higher than 25 m/s may be allowed following con‐
sultation with the manufacturer. 
 Within a low‐pressure range of up to approx. 250 mbar, a maximum flow rate 
of approx. 15 to 20 m/s is recommended at the sensing point. On a case‐by‐case basis, 
and following consultation with the manufacturer, even lower flow rates may be al‐
lowed. 
 
Basics for installing the device in a pipe 
 
27 