1.7 Electrical connections

1.7.1
Connecting-up induction motors
Note
The motors can be fed from a DC link voltage of up to 700 V DC. For shaft heights
180 and 225, the appropriate version must be selected.
Table 1-7
Overview, connection system for 1PH7 motors
SH
Number
Max. cross-section that can be
of main
connected
terminals
100
6 x M5
25 mm
132
6 x M6
35 mm
160
6 x M6
50 mm
180
3 x M12
2 x 50 mm
225
3 x M12
2 x 50 mm
Power cable
The power cables for 1PH motors are selected according to the rated motor cur-
at +40 °C according to Table 1-8.
rent I
N
Caution
!
Carefully observe the current which the motor draws for your particular application!
Adequately dimension the connecting cables according to IEC 60204-1.
Note
The cables are available in a UL version or for higher mechanical requirements.
Technical data, refer to Catalog, Chapter "Connection System".
1) Cable cross-section, corresponding to the line conductor cross-section
2) Cable lug acc. to DIN 46234
 Siemens AG, 2004. All rights reserved
Induction Motors, 1PH7 (APH7S) – 05.04 Edition
2
2
with cable lug connection
2
with cable lug connection
2
with cable lug connection
2
with cable lug connection
Motor Description
1.7 Electrical connections
Terminal strip
PE connection size/
for temperature
cable lug width
sensor
3 terminals
M5/9 mm
3 terminals
M6/15 mm
3 terminals
M6/18 mm
4 terminals
Without cable lug using a
terminal clamp
4 terminals
Without cable lug using a
terminal clamp
2)
1)
1)
1PH7/1-23