Additional Notes - Siemens RXZ90.1 Manual

Desigo rx, receiver with pps2 interface
Hide thumbs Also See for RXZ90.1:
Table of Contents

Advertisement

Additional notes:

Installation mode
Different ways of setting
the receiver to installa-
tion mode
Diagnostics and the diagnostic plug
Tool socket
Series resistors
R = 11.2k
6 / 10
Siemens
Building Technologies
The room unit starts in installation mode each time batteries are inserted (after min.
30s off load)
When there are no room units in its device list, the receiver starts in installation mode
when the power supply is connected. It scans for installation signals for 3 ½ minutes,
and identifies all room units in installation mode within its receiver range
The first 5 room units identified are entered in the device list of the receiver
For each receiver, a delay must precede the process of establishing communication,
as the receiver can also pick up signals from other room units in the vicinity
 Wait at least 4 minutes between each new installation sequence
A Receiver with at least one room unit in its device list will not switch to installation
mode after a power failure, but continue normal operation with the associated room
units.
Connecting the receiver to the power supply (power ON) when the device list is
empty (snap-mount RXZ90.1 receiver on mounting plate)
Connecting the controller to the power supply, when the receiver is connected to
the controller and its device list is empty
With fewer than 5 room units registered, connecting the diagnostic plug to the
receiver and pressing the button briefly ( < 1s)
Plugging the RXT20.1 service terminal into the receiver with an empty device list,
and pressing the service pin on the RXT20.1 >4s
Sustained pressure (>5s) on the button of an existing room unit. The receiver will
delete this room unit from its device list and then switch to installation mode
The process of establishing communication (receiver status) can be monitored by
connecting the diagnostic plug to the receiver.
The plug can be assembled in-house or ordered from your national Landis & Staefa
office. It is an aid for the service staff and cannot be purchased normally.
Connections 3 and 4 are short-circuited by a pushbutton
Connections 5 (+) and 6 (–) are used to operate a red LED
Connections 7 and 8 are used to operate the green LEDs
(One of the two green LEDs will light up, depending on the polarity of the bus power
supply)
8
7
6 5
4 3 2 1
LEDs (2mA)
Button
2x green
1x red
RXZ90.1 – Receiver with PPS2 interface
RJ45 telephone-type socket
Cable (8-wire)
Green LED (<2mA)
Green LED (Optional,
lights up in event of
incorrect polarity)
00495
Red LED
Pushbutton
CA2N1644en_05