Table 13 Electrical Specifications W**Hc - Bard 11EER WH Series Installation Instructions Manual

Wall mount
Hide thumbs Also See for 11EER WH Series:
Table of Contents

Advertisement

Rated
Model
Volts &
Phase
W42HC-A00, A0Z
A04
A05
230/208-1
A10
 A15
W42HC-B00, B0Z
B05
230/208-3
B09
 B15
W42HC-C00, C0Z
C05
460-3
C09
 C15
W48HC-A00, A0Z
A04
A05
230/208-1
A10
 A15
 A20
W48HC-B00, B0Z
B05
B09
230/208-3
 B15
 B18
W48HC-C00, C0Z
C05
460-3
C09
 C15
W60HC-A00, A0Z
A05
A10
230/208-1
 A15
 A20
W60HC-B00, B0Z
B09
230/208-3
 B15
 B18
W60HC-C00, C0Z
C09
460-3
 C15
 The "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION: When more than one (1) field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway.
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Maximum KW that can operate with the heat pump on is 9KW. Full heat available during emergency heat mode.
 Maximum KW that can operate with the heat pump on is 10KW. Full heat available during emergency heat mode.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Electrical Specifications − W**HC Series
Single Circuit
No. Field
Maximum
Power
Minimum
External
Circuits
Circuit
Fuse or
Ampacity
Ckt. Brkr.
1
32
45
1
52
60
1
58
60
1 or 2
84
90
1 or 2
84
90
1
24
35
1
39
45
1
51
60
1
51
60
1
12
15
1
21
25
1
25
30
1
26
30
1
35
50
1
56
60
1 or 2
61
70
1 or 2
87
90
1 or 2
87
90
1 or 2
111
125
1
25
35
1
43
50
1
53
60
1
53
60
2
N/A
N/A
1
12
15
1
20
20
1
25
30
1
26
30
1
42
60
1 or 2
67
80
1 or 2
94
100
1 or 2
94
100
1 or 2
112
125
1
29
40
1
56
60
1
56
60
2
N/A
N/A
1
14
20
1
28
30
1
28
30
TABLE 13
 Minimum
Field
Circuit
Power
Ground
Ampacity
Wire
Wire
Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
8
10
6
10
6
10
4
8
32
52
4
8
32
52
8
10
8
10
6
10
6
10
14
14
10
10
10
10
10
10
8
10
6
10
6
8
35
26
3
8
35
52
3
8
35
52
2
6
58
52
8
10
8
10
6
10
6
10
N/A
N/A
52
28
14
14
10
10
10
10
10
10
8
10
4
8
41
26
3
6
47
52
3
6
47
52
2
6
60
52
8
10
6
10
6
10
N/A
N/A
55
28
12
12
8
10
8
10
Multiple Circuit
 Maximum
External
Field Power
Fuse or
Wire Size
Ckt. Breaker
45
60
8
6
10
45
60
8
6
10
40
30
8
10
10
50
60
8
6
10
50
60
8
6
10
60
60
6
6
10
60
30
6
10
10
40
30
8
10
10
60
60
8
6
10
60
60
8
6
10
60
60
6
6
10
60
30
6
10
10
Manual 2100-711C
Page
Ground
Wire Size
10
10
10
10
10
10
10
10
10
10
10
10
35 of 45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents