Step 11 - Adjust Factory-Installed Options; Step 12 - Install Accessories; Step 13 - Check Belt Tension; Belt Force - Deflection Method - Carrier WeatherMaker 50TC Series Installation Instructions Manual

18-29 single package rooftop with cooling only horizontal airflow unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaker 50TC Series:
Table of Contents

Advertisement

ECONOMIZER
Step 11 — Adjust Factory-Installed Options
ECONOMI$ER
®
IV OCCUPANCY SWITCH
Refer to Fig. 66 for general EconoMi$er IV wiring. External occu-
pancy control is managed through a connection on the Controls
Connections Board.
If external occupancy control is desired, connect a time clock or
remotely controlled switch (closed for Occupied, open for Unoc-
cupied sequence) at terminals marked OCCUPANCY on CTB.
Remove or cut jumper JMP 2 to complete the installation.
Step 12 — Install Accessories
Available accessories include:
Roof curb
Thru-base connection kit (must be installed before unit is
set on curb)
Manual outside air damper
Two-position motorized outside air damper
EconoMi$er 2 (without control/for external signal and in-
tegrated barometric relief)
EconoMi$er IV (with control and integrated barometric
relief)
Power exhaust
Differential dry-bulb sensor (EconoMi$er IV)
Outdoor enthalpy sensor
Differential enthalpy sensor
Electric Heaters
Single Point Kits
Low Ambient Controls
Thermostat/Sensors
CO
sensor
2
2 POSITION DAMPER
Fig. 66 — EconoMi$er
®
DDC interface (PremierLink)
Louvered hail guard
Phase monitor control
Winter start kit
Refer to separate installation instructions for information on in-
stalling these accessories.
Step 13 — Check Belt Tension
Measure the belt span length as shown in Fig. 67. Calculate the re-
quired deflection by multiplying the belt span length by
example, if the belt span length is 32 inches:
32 x
BELT FORCE — DEFLECTION METHOD
Check the belt tension with a spring-force belt force deflection
gage (available from drive belt manufacturer).
1.
Place a straightedge along the belt between the two pulleys.
Measure the distance between the motor shaft and the blower
shaft.
2.
Set the tension gage to the desired tension (see Table 1 in
Fig. 67). Place the large O-ring at that point.
3.
Press the tension checker downward on the belt until the large
O-ring is at the bottom of the straightedge.
4.
Adjust the belt tension as needed.
Adjust belt tension by loosing the motor mounting plate front bolts
and rear bolt (see Fig. 68) and slide the plate towards the fan (to
reduce tension) or away from the fan (to increase tension). Ensure
the blower shaft and motor shaft are parallel to each other (pulleys
aligned). Tighten all bolts securely when finished.

BELT TENSION METHOD

Requires belt tension gage that measures tension in belt in units of
lbs force (see Fig. 67).
57
UNIT WITHOUT ECONOMIZER OR
2 POSITION DAMPER
IV Wiring
/
=
/
inch deflection.
1
1
64
2
/
. For
1
64

Hide quick links:

Advertisement

Table of Contents
loading