DI 2 Delay
DI 3 Polarity
DI 3 Config
DI 3 Delay
LIGHTS ON
DEFROST START
DEVICE DISABLE
SETPOINT SHIFT
Defrost Synch
Defr End Synch
Set Point Synch
Display Synch
Document Part # 026-4275 Rev 0
©2019 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
d2d - Input delay or alarm
delay
i3P - Digital input 3
polarity
i3F - Digital input 3
configuration
d3d - Input delay or alarm
delay
Command input of lights
on
Command input of defrost
on
Command input of device
disable
Command input of energy
savings
LMd - LAN Defrost
synchronization
dEM - LAN Defrost
termination sync
LSP - LAN setpoint
synchronization
LdS - LAN display
synchronization
Table 2 - XM670K_50 Property Help Explanations
Sets delay of activation for the input configured.
CL = The input is activated by closing the contact; OP = The input is
activated by opening the contact.
Selects 3rd Digital Input configuration for sequence. When set to Door
Switch, the device will obey E2 property setting Door Sw Mode (odC) and
shut down refrigeration and/or fan relay outputs, and resume normal
operation when door switch deactivates. If Door Switch stays in active
state for longer than DI 1 DELAY (did) setting, the device will alarm and
the refrigeration and/or fan relay outputs will turn back on if DOOR ALM
RESTART (rrd) is set to YES. The local display will show dA. When set to
Light Switch, the change of state of the digital input will turn the light ON
or OFF, depending on how polarity and delay are set. If Light Switch is
chosen, the Lights On property of the Inputs tab has to be mapped
(pointed) as an input from the same application and its respective digital
input 3 output property in the Outputs tab. If set to Device On/Off, the
change of state of the digital input will turn the device ON or OFF,
depending on how polarity and delay are set. If Device On/Off is chosen,
the Device Disable property in the Inputs tab has to be mapped (pointed)
as an input from the same application and its respective digital input 3
output property in the Outputs tab. If Set Point Shift is chosen, the
SetPoint Shift property in the Inputs tab has to be mapped (pointed) as
an input from the same application and its respective digital input 3
output property in the Outputs tab.
Sets delay of activation for the input configured.
Defaulted to fixed value of ON. This can be configured to use a pointer in
from another E2 application digital value output into this property as its
ON/OFF input to which will command the device light output relay to an
ON or OFF state.
Example: Time schedule output can be pointed into this property as its
ON/OFF input which will command device light output relay.
Defaulted to fixed value of OFF. This can be configured to use a pointer in
from another E2 application digital value output into this property as its
ON/OFF input to which will command the device into a defrost sequence.
Example: Time schedule output can be pointed into this property as its
ON/OFF input which will command device into a defrost start sequence.
Defaulted to fixed value of ON. This can be configured to use a pointer in
from another E2 application digital value output into this property as its
ON/OFF input to which will command the device light output relay to an
ON or OFF state. An OFF command will turn the device off.
Defaulted to fixed value of ON. This can be configured to use a pointer in
from another E2 application digital value output into this property as its
ON/OFF input to which will command the device light output relay to an
ON or OFF state. An OFF command will turn the device off.
Not used.
Not used.
Not used.
Not used.