The Standard Circuit sets the Defrost Schedule and
can provide temperature alarming. The Standard
Circuit is displayed on the E2 Home screen under
Circuits. Once a defrost begins, the XM670K_50
device application will execute the defrost
sequence. Once it has met its settings to end a
defrost, it will then signal the Standard Circuit that
defrost has ended, updating the Standard Circuit.
The Standard Circuit only provides temperature
setpoint and does not control refrigeration.
Standard Circuit
Setpoint:
Active Setpoint
>>>>>>>>>>>
Case Temp
Case Temp 1
<<<<<<<<<<<<
Defrost
Defrost Output
>>>>>>>>>>>>
Defrost
Defrost Term
Termination
DV 1 (input)
Table 1 - XM670K_50 and Standard Circuit Inputs and Outputs
1. Each E2 property in the XM670K_50 has
property help to aid in understanding.
Highlight a property and press the
get more details.
Figure 43 - Setpoint Property
Document Part # 026-4275 Rev 0