(4) Fuse reset(DSW 6)
Factory Setting.
ON
OFF
1 2
In the case of applying high voltage to the
terminal 1,2 of TB2, the fuse (0.5A) on the PCB is
cut.
In such case, firstly cut off high voltage, connect
communcation cable,and then turn on NO.1 pin.
ON
OFF
1 2
(5)Unit function setting (DSW7).
No setting is required.
ON
3 4
OFF
1 2
(6) Refrigeration system no. setting (DSW8)
Setting is required
Set with binary method and setting positions
before shipment are all OFF.
ON
OFF
1 2
3 4 5 6
Max No.64 are available to set when all
the equipment to be connected are
corresponding to Hi-net
Ex.) Set refrigeration system no. as 8
ON
OFF
1 2
3 4 5 6
(7) Address setting (DSW9)
Setting is required
Set with binary method and setting positions
before shipment are all OFF.
ON
OFF
1 2
3 4 5 6
Max No.64 are available to set when all the
equipment to be connected are
corresponding to Hi-net
Ex.) Set refrigeration system no. as 10
ON
OFF
1 2
3 4 5 6

14. Test Run

Commissioning and test run is made as recorded
in table 14.1.

14.1 Check BeforeTest Run

Power off before wiring. After the unit is mounted,
Check before leakage protector starts:
1. On-site wiring
The wiring between outdoor unit and water
module, water module and electronic three-way
valve, water module and domestic water tank
(optional) are made according to the wiring
diagram and national regulations.
2. Fuse or protection device
Check the dimension and type of fuse or
protection device installed on site are conforming
to technical specification in table 10.1. Confirm
that the fuse and protection device are not
bypassed.
3. Earth wire
ensure earth wire is connected and conforming
to requirements.
4. Inner wiring
Check no loose connector or damaged electrical
component inside electrical box.
5. Fixation
Check the unit is fixed, avoiding abnormal noise
and vibration when the unit is started.
6. Damaged parts
Check no damaged component or pressed pipe
inside the unit.
7. Refrigerant leakage
Check no refrigerant leakage inside unit. If
occurs, contact local dealer.
8. Power voltage
Check on-site power voltage that must be
consistent with voltage value in unit name plate.
9. Vent valve
Ensure vent valve is opened and screwed by two
circles at least.
10. Safety valve
Check system is fully injected with water. When
safety valve is manually opened, water rather
than air is drained.
11. Ball valve
Ensure ball valve is correctly installed and fully
opened. Closing valve running system will
damage water pump.
12.
Electronic three-way valve
Ensure wiring method of electronic three-way
valve and installation direction of valve body are
conform to requirements.