Pipe Connection Method Between Outdoor Unit/Indoor Unit - LG MULTI V 5 ARUN120BTE5 Installation Manual

Heat pump
Table of Contents

Advertisement

1,MFL67221438,영영 2018. 10. 4. 영영 11:29 Page 14
14
Header Method
Ⓐ : Outdoor Unit
Ⓑ : Header branch
Ⓒ : Indoor Units
Ⓓ : Sealed piping
Ⓔ : Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ : Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ : Connection branch pipe
between Outdoor
units : ARCNN21
Pipe Connection Method between outdoor
unit/indoor unit
Master
L2
L3
E
Indoor
Unit
1st branch
l 40m (131ft)
h 40 m (131 ft)
h See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
WARNING
!
• Branch pipe can not be used after header.
• It is recommended that difference in length of the pipes con-
nected to the indoor units (a~f) is minimized. Performance dif-
ference between indoor units may occur.
Level Difference
(Outdoor unit ↔ Outdoor unit)
Max length from first branch to
each outdoor unit (L1, L2, L3)
(Table 1) Limit Pipe length
Longest
pipe
length(L)
Outdoor Unit
Max pipe
Equivalent
length
Indoor Unit
pipe length
Total pipe
length
Outdoor Unit
Difference in
Max
↔ Indoor Unit
height(H)
difference
Indoor Unit
Difference in
in height
↔ Indoor Unit
height(h)
Longest pipe
Pipe
length after
length(ℓ)
1st branch
h * : See Table 4
ODU Capacity
Slave3
Slave2
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave1
Master
10m or
less
G
F
E
L 200 m [656 ft]
B
l 40 m [131 ft]
D
C
C
C
C
C
h 40 m (131 ft)
Slave1
Slave2
Slave3
H1
F
G
L1
Refrigerant pipe diameter from outdoor unit to first branch
5 m [16.4 ft]
Less than 10 m [32.8 ft]
(equivalent length of piping 13 m
[42.7 ft])
Combination of Y
Y branch
branch/header
Method
Method
Method
A+B+C+D+e ≤ 150 m
A+B+b ≤ 150 m [492 ft]
A+C+e ≤ 150 m [492 ft]
A+f ≤ 200 m
[492 ft]
(200 m [656 ft] : Condi-
(200 m [656 ft] : Condi-
tional application)*
tional application)*
175 m [574 ft]
175 m [574 ft]
(225 m [738 ft] : Condi-
(225 m [738 ft] : Condi-
tional application)*
tional application)*
1000 m [3281 ft]
1000 m [3281 ft]
110 m [361 ft]
110 m [361 ft]
110 m [361 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
(90 m [295 ft] : Condi-
(90 m [295 ft] : Condi-
40 m [131 ft]
tional application)*
tional application)*
WARNING
!
Increased Pipe Diameter(table 2)
- When pipe length is 90m [295 ft] or more from ODU to 1st
branch
- When level difference is 50 m [164 ft] or more
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
C
Pipe diameter when pipe
length is < 90m (295ft)
ODU
(Standard)
capacity
(hp)
Liquid Pipe
Gas Pipe
mm (inch)
mm (inch)
8
Ø9.52 (3/8) Ø19.05 (3/4) Ø12.7 (1/2)
10
Ø9.52 (3/8)
Ø22.2 (7/8)
12~16
Ø12.7 (1/2) Ø28.58 (1-1/8) Ø15.88 (5/8) Ø34.9 (1-3/8) Ø15.88 (5/8) Not increased
18~22
Ø15.88 (5/8) Ø28.58 (1-1/8) Ø19.05 (3/4) Ø34.9 (1-3/8) Ø19.05 (3/4) Not increased
24
Ø15.88 (5/8) Ø34.9 (1-3/8) Ø19.05 (3/4) Ø41.3 (1-5/8) Ø19.05 (3/4) Not increased
26~34
Ø19.05 (3/4) Ø34.9 (1-3/8) Ø22.2 (7/8) Ø41.3 (1-5/8) Ø22.2 (7/8) Not increased
36~60
Ø19.05 (3/4) Ø41.3 (1-5/8) Ø22.2 (7/8) Ø44.5 (1-3/4) Ø22.2 (7/8) Not increased
62~64
Ø22.2 (7/8) Ø44.5 (1-3/4)
66~96
Ø22.2 (7/8) Ø53.98 (2-1/8) Ø25.4 (1) Ø53.98 (2-1/8) Ø25.4 (1) Not increased
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Downward indoor unit
total capacity [kW(Btu/h)]
≤ 5.6(19,100)
< 16.0 (54,600)
≤ 22.4 (76,400)
< 33.6 (114,700)
< 50.4 (172,000)
< 67.2 (229,400)
< 72.8(248,500)
< 100.8(344,000)
< 173.6(592,500)
< 184.8(630,700)
≤ 224.0(764,400)
(Table 4) Conditional Application
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Condition
Diameter of pipes be-
tween first branch and the
last branch should be in-
1
creased by one step, ex-
cept pipe diameter B,C,D
Header
is same as Diameter A
While calculating whole re-
frigerant pipe length, pipe
2
B,C,D length should be cal-
[656 ft]
culated twice.
Length of pipe from each
225 m
3
indoor unit to the closest
[738 ft]
branch
1000 m
Length of pipe from out-
[3281 ft]
door unit to the farthest
indoor unit 5
4
(A+B+C+D+e)] - [Length
of pipe outdoor unit to the
closest indoor unit 1
(A+a)] ≤ 40 m [131 ft]
Pipe diameter when height differ-
Pipe diameter when pipe
length is ≥ 90m (295ft)
ential (ODU↔IDU) is > 50m (164ft)
Liquid Pipe
Gas Pipe
Liquid Pipe
mm (inch)
mm (inch)
mm (inch)
Ø22.2 (7/8)
Ø12.7 (1/2) Not increased
Ø12.7 (1/2) Ø28.58 (1-1/8) Ø12.7 (1/2) Not increased
Ø25.4 (1) Ø53.98 (2-1/8) Ø25.4 (1) Not increased
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø6.35(1/4)
Ø12.7(1/2)
Ø9.52(3/8)
Ø15.88(5/8)
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø34.9(1-3/8)
Ø19.05(3/4)
Ø34.9(1-3/8)
Ø19.05(3/4)
Ø41.3(1-5/8)
Ø22.2(7/8)
Ø44.5(1-3/4)
Ø22.2(7/8)
Ø53.98(2-1/8)
Example
Ø6.35(1/4) ' Ø9.52(3/8), Ø9.52(3/8) '
Ø12.7(1/2), Ø12.7(1/2) ' Ø15.88(5/8),
40 m [131 ft] <
Ø15.88(5/8) ' Ø19.05(3/4), Ø19.05(3/4) '
B+C+D+e
Ø22.2(7/8), Ø22.2(7/8) ' Ø25.4(1),
90 m [295 ft] ' B, C, D
Ø25.4(1) ' Ø28.58(1-1/8), Ø28.58(1-1/8) '
Ø31.8(1-1/4), Ø31.8(1-1/4) ' Ø34.9(1-3/8),
Change a diameter
Ø34.9(1-3/8) ' Ø38.1(1-1/2)
A+Bx2+Cx2+Dx2
+a+b+c+d+e ≤
1 000 m [3 281 ft]
a,b,c,d,e ≤ 40 m
[131 ft]
L
l
(A+B+C+D+e)-
(A+a) ≤ 40 m
h 40 m [131 ft]
[131 ft]
Gas Pipe
mm (inch)
Indoor
Unit