3. Outdoor fan control
Up
GP110 to
GP160
Down
3-1) Cooling fan control
The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency.
The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).
Only for 60 seconds after the operation has started, the maximum fan tap corresponding to the
zone in the following table is fixed and then the fan is controlled by temperature of TL sensor.
TL [˚C]
58
55
+1 tap / 20 sec
Up to the maximum
revolution frequency of each zone
38
Revolution frequency hold
35
–1 tap / 20 sec
Up to the minimum
revolution frequency of each zone
3-2) Heating fan control
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.
(Control from minimum W1 to maximum (according to the following table))
For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in
the following table is fixed and then the fan is controlled by temperature of TE sensor.
TE [˚C]
–2 taps / 20 sec. (Up to W1)
Stop timer count
24
–2 taps / 20 sec. (Up to W1)
21
–1 tap / 20 sec. (Up to W1)
18
Revolution frequency hold
15
+1 tap / 20 sec
(Up to the maximum tap of each zone)
Object: GP140 (GP160)
or lower
Temp. range
10˚C ≤ TO
5˚C ≤ TO < 10˚C
–3˚C ≤ TO < 5˚C
WB (WC)
–10˚C ≤ TO < –3˚C
TO < –10˚C
TO trouble
Revolution frequency allocation of fan taps [rpm]
W1
W2
W3
W4
200
240
240
260
200
280
WE tap
20 Hz
20Hz
to 45Hz
or higher
Max.
Max.
W7
W8
W9
WA
WB (WC)
WB (WC)
WC
WC
WD
WD
WD
WD
W5
W6
W7
320
380
480
360
400
500
Temp. range
38˚C ≤ TO
29˚C ≤ TO < 38˚C
15˚C ≤ TO < 29˚C
5˚C ≤ TO < 15˚C
0˚C ≤ TO < 5˚C
–4˚C ≤ TO < 0˚C
TO < –4˚C
TO trouble
When TE ≥ 24°C continues for 5 minutes, the
compressor stops.
It is the same status as the normal thermostat-
OFF without trouble display.
The compressor restarts after approx. 2 minutes
30 seconds and this intermittent operation is not
abnormal.
In case that the status in item
frequently, stain on filter of the suction part of the
indoor unit is considered.
Clean the filter and then restart the operation.
45Hz
Temp. range
Max.
10˚C ≤ TO
W9
5˚C ≤ TO < 10˚C
–3˚C ≤ TO < 5˚C
WC
–10˚C ≤ TO < –3˚C
WC
WD
TO < –10˚C
WD
TO trouble
– 41 –
W8
W9
WA
WB
500
530
610
640
520
550
630
660
20 Hz
20Hz
or lower
to 45Hz
Min. Max. Min. Max. Min. Max.
W6
WC
W8
W5
WB
W7
W4
W8
W6
W3
W6
W5
W2
W4
W4
W2
W3
W3
W1
W2
W1
W1
WC
W1
Object: GP110
20 Hz
or lower
to 45Hz
Max.
W7
W9
WA
WC
WD
WD
WC
WD
WE
660
720
780
700
740
820
45Hz
or higher
WD
WA
WD
WC∗
W9
WC
WA
W8
WC
W8
W7
WA
W6
W5
W8
W5
W4
W6
W4
W2
W6
WD
W2
WD
∗ : WB for GP110
generates
20Hz
45Hz
or higher
Max.
Max.
W8
W9
WA
WA
WA
WC
WC
WC
WD
WD
WD
WD