Product Data; External Static Pressure & Air Flow - LG ANNQ60GKA4 Installation Manual

Single ducted split
Table of Contents

Advertisement

PRODUCT DATA

22
PRODUCT DATA
External Static Pressure & Air Flow
Flow rate
(CFM)
0.1
Max (1 750)*
90
High (1 400)
77
Middle (1 260)
70
Low (1 000)
61
- Air handler units are UL Listed up to 0.5 in.wc external static pressure, including air filter, set
coil, unless otherwise noted.
- in.wc = inch Water Column, inAq
High static pressure is 0.3 in.wc (Factory set Default)
Low static pressure is 0.1 in.wc
- If you set ESP incorrectly, the air conditioner may cause cooling & heating capacity down and
malfunction.
* : Max setting is only available for ANNQ60GKA4.
Setting Value @ ESP(in.wc)
0.2
0.3
0.4
95
100
105
82
87
94
77
83
90
67
75
82
0.5
0.6
0.7
-
-
-
100
102
106
96
98
104
88
94
100
0.8
0.9
1.0
-
-
-
110
116
116
108
114
116
104
112
116