Dip Switch Configuration - Siemens QAM2151.040/MO Basic Documentation

Duct temperature, humidity and air quality sensors, immersion temperature sensor, modbus rtu (rs-485)
Table of Contents

Advertisement

Configurations
4

DIP switch configuration

4.6 DIP switch configuration
DIP1
Address configuration
12 | 16
The Modbus setting can be configured via DIP switches when DIP2-position 7 is
ON.
NOTICE
Modbus registers 764...768 are not writable via a master under DIP switches
configuration.
The sensor has two sets of DIP switches: DIP1 and DIP2.
2
2
2
7
6
5
1
2
3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
...
...
...
ON
ON
ON
NOTES:
Modbus address configuration: Valid address range 1...247, others = 0
If an invalid address is set, the newly set values of register 764...768 are not
activated. The registers keep the previous value.
2
2
2
4
3
2
4
5
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
...
...
...
ON
ON
ON
2
2
Address
1
0
7
8
OFF
OFF
0
(default)
OFF
ON
1
ON
OFF
2
ON
ON
3
OFF
OFF
4
...
...
...
ON
ON
255
A6V11610643_en--_a