Economi$Er Systems - Bryant 581J-17-28 Service And Maintenance Instructions

Gas heat rooftop package nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

ECONOMI$ER SYSTEMS

IMPORTANT:
Any
economizer
economizer requirements as laid out in California's Title
24
mandatory
section
diagnostics) and/or prescriptive section 140.4 (life−cycle
tests, damper leakage, 5 year warranty, sensor accuracy,
etc), will have a label on the economizer. Any economizer
without this label does not meet California's Title 24. The
five year limited parts warranty referred to in section
140.4 only applies to factory installed economizers. Please
refer to your economizer on your unit.
The 581J units may be equipped with a factory−installed
or accessory (field−installed) EconoMi$er system. Two
types are available: with a logic control system
(EconoMi$er
IV)
and
(EconoMi$er2). See Fig. 61 and Fig. 62 for component
locations on each type. See Fig. 59 and Fig. 60 for
EconoMi$er section wiring diagrams. Both EconoMi$ers
use direct−drive damper actuators.
LEGEND
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT — Potentiometer
RAT — Return-Air Temperature
that
meets
120.2
(fault
detection and
without
a
control
system
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
8
7
Potentiometer Defaults Settings:
Power Exhaust
Middle
Minimum Pos.
Fully Closed
DCV Max.
Middle
DCV Set
Middle
Enthalpy
C Setting
Fig. 60 − EconoMi$er IV Wiring
the
WIRING
HARNESS
ACTUATOR
ECONOMI$ER2
PLUG
BAROMETRIC
RELIEF
DAMPER
Fig. 59 − EconoMi$er IV Component Locations
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
47
ECONOMIER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
C06021
OUTDOOR
AIR HOOD
HOOD
SHIPPING
BRACKET
GEAR DRIVEN
DAMPER
C06022
C06028

Advertisement

Table of Contents
loading

Table of Contents