Bryant 581J-17-28 Service And Maintenance Instructions page 44

Gas heat rooftop package nominal 15 to 25 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

TERMINAL LABEL
INPUTS
RT, C
SS
FS, T1
W
RS
LS
CS
OUTPUTS
L1, CM
IFO
GV
NATURAL GAS
ELEVATION
Feet
Meters
0 - 2000
0-610
2000
610
3000
914
4000
1219
5000
1524
6000
1829
7000
2134
8000
2438
9000
2743
10000
3048
11000
3353
12000
3658
13000
3962
14000
4267
PROPANE GAS
ELEVATION
Feet
Meters
0 - 2000
0-610
2000
610
3000
914
4000
1219
5000
1524
6000
1829
7000
2134
8000
2438
9000
2743
10000
3048
11000
3353
12000
3658
13000
3962
14000
4267
* As height above sea level increases, there is less oxygen per cubic ft. of air. Therefore, reduce heat input rate at higher altitudes.
1
XX
= CRNGELEV001A00
XX
Table 15 – IGC Connections
POINT DESCRIPTION
Input power from TRAN 1
Speed sensor
Flame sensor
Heat stage 1
Rollout switch
Limit switch
Centrifugal switch (not used)
Induced draft combustion motor
Indoor fan
Gas valve (heat stage 1)
Table 16 – Altitude Compensation* (17 − 30) – Natural Gas
220k BTUH
Orifice
Input
Size
(btu/hr)
30
220,000
30
202,400
1
31
193,600
1
31
184,800
1
31
176,000
1
31
167,200
1
32
158,400
1
32
149,600
1
34
140,800
2
35
132,000
2
37
123,200
2
37
114,400
2
39
105,600
2
39
96,800
Table 17 – Altitude Compensation* (17 − 30) – Propane Gas
220k BTUH
Orifice
Input
Size
(btu/hr)
5
48
220,000
3
49
202,400
3
49
193,600
3
49
184,800
3
50
176,000
3
50
167,200
3
50
158,400
3
51
149,600
3
51
140,800
4
52
132,000
4
52
123,200
4
53
114,400
4
53
105,600
4
53
96,800
2
3
= CRNGELEV002A00
XX
SENSOR LOCATION
control box
gas section
gas section
LCTB
gas section
fan section
gas section
control box
gas section
NOMINAL HEAT INPUT
310k BTUH
Orifice
Size
30
30
1
31
1
31
1
31
1
31
1
32
1
32
1
34
1
35
2
37
2
37
2
39
2
39
NOMINAL HEAT INPUT
310k BTUH
Orifice
Size
5
48
3
49
3
49
3
49
3
50
3
50
3
50
3
51
3
51
4
52
4
52
4
53
4
53
4
53
4
= CRLPELEV006A00
XX
= CRLPELEV006A00
44
TYPE OF I/O
PIN NUMBER
24 VAC
analog input
switch input
24 VAC
switch input
switch input
switch input
line VAC
relay
relay
400k BTUH
Input
Orifice
(btu/hr)
Size
310,000
30
285,200
30
1
272,800
31
1
260,400
31
1
248,000
31
1
235,600
31
1
223,200
32
1
210,800
32
1
198,400
34
1
186,000
35
2
173,600
37
2
161,200
37
2
148,800
39
2
136,400
39
400k BTUH
Input
Orifice
(btu/hr)
Size
5
310,000
48
3
285,200
49
3
272,800
49
3
260,400
49
3
248,000
50
3
235,600
50
3
223,200
50
3
210,800
51
3
198,400
51
4
186,000
52
4
173,600
52
4
161,200
53
4
148,800
53
4
136,400
53
5
XX
= CRLPKIT9001A00
J1, 1‐3
J2, 2
J2, 5‐6
J2, 7‐8
J2, 9‐10
J2, 1
J2, 11‐12
Input
(btu/hr)
400,000
368,000
352,000
336,000
320,000
304,000
288,000
272,000
256,000
240,000
224,000
208,000
192,000
176,000
Input
(btu/hr)
400,000
368,000
352,000
336,000
320,000
304,000
288,000
272,000
256,000
240,000
224,000
208,000
192,000
176,000