Honeywell FocusPRO TH6220D Installation Manual page 6

Hide thumbs Also See for FocusPRO TH6220D:
Table of Contents

Advertisement

Installation
Guide
o
"
CAUTION:
ELECTRICAL
HAZARD.
Can cause electrical
shock or equipment
damage.
Disconnect
power before wiring.
-L
E Aux
G O/B
C
Y
R
Rc
Heat Pump
Conventional
NOTES
R & Rc termirtals
In single-transformer
system,
leave metal
jumper
in place between
R & Rc. Remove
metal jumper
if two-transformer
system.
C terminal
The C (common
wire) terminal
is optional
when thermostat
is powered
by batteries,
W (O/B) terminal
If thermostat
is configured
for a heat pump
in the Installer
Setup, configure
changeover
valve for cool ("O" factory setting) or heat
("B").
L terminal
(Output)
Heat pump reset. L terminal
powered contin-
uously when thermostat
is set to Em Heat.
Configure
thermostat
for 2 heat / 1 cool heat
pump in the Installer Setup.
Wire
specifications
Use 18- to 22-gauge
thermostat
wire.
Shielded cable is not required.
Wiring
1
Loosen screw terminals, insert
wires into terminal block, then
re-tighten screws.
2
Push excess wire back into the
wall opening. Keep wires in shaded
area as shown at left.
Plug the wall opening with non-
flammable
insulation
to prevent
drafts from affecting thermostat
operation.
Terminal
Designations
Conventional
Terminal
Letters:
Y2
2rid stage compressor
contactor
W2
2nd stage heat relay
G
Fan relay
W
1st stage heat relay
C
Common
wire from secondary
side of
cooling system transformer
Y
1st stage compressor
contactor
R
Heating power. Connect to secondary
side of heating system transformer.
Rc
Cooling power. Connect to secondary
side of cooling
system transformer.
Heat Pump Termirtal
Letters:
L
Heat pump reset. L terminal
powered
continuously
when System is set to Em
Heat.
E
Emergency
heat relay
Aux Auxiliary
heat relay
G
Fan relay
O/B Changeover
valve for heat pumps
C
Common
wire from secondary
side of
cooling system transformer.
Y
Compressor
contactor
R
Heating power. Connect to secondary
side of heating system transformer.
Rc
Cooling power. Connect to secondary
side of cooling
system transformer.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents