Protective conductor connection and potential equalization

Requirement
You have mounted the Control Unit in the control cabinet.
The SIMOTION D4x5-2 Control Unit has a connection for the protective conductor and a
connection for the equipotential bonding conductor (M5 screw, Torx T25). Only one connection
is available for the CX32-2 - this must be used both for the protective conductor and the
equipotential bonding conductor.
Note
Requirements for functional safety for machines and systems; reliability and EMC are only
guaranteed with original SIEMENS cables.
Note the following safety information:
Danger to life from energized parts
Death or serious injury will result if energized parts are touched.
Turn off and lock out all power supplying this device before working on this device.
Protective conductor connection
SIMOTION D and the SINAMICS S120 drive system are designed for use in cabinets with a
protective conductor connection.
All system components and machine parts must be incorporated in the protection concept.
The drive line-up must be arranged on a common bright mounting plate
with the EMC limit values. The connection
mounting plate.
The mounting plate must be connected to the protective conductor connection of the control
cabinet. For this purpose, a connection
. The protective conductor bar
The protective connection (PE connection) that is used for the motors
through the motor cable.
For EMC reasons, the motor cable shield must be laid flat at both the Motor Module (MM) /
Power Module (PM) and motor.
A protective connection
with low impedance (e.g. control cabinet door via hinges
Example: Booksize axis grouping comprising Control Unit (CU), Line Module (LM), and Motor
Modules (MM) as well as drive in blocksize format comprising a Power Module (PM) with
snapped on Control Unit (CU)
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
DANGER
must also be established for components that are not connected
4.2 Protective conductor connection and potential equalization
establishes a low-impedance connection to the
must be established to the protective conductor bar
must be connected to the protective conductor
in order to comply
must be established
).
Connecting
.