TLC3-ECO Economizer
Applications
Economizer:
Control of outdoor
damper
General
TLC3-ECO: 1 independent temperature control loop with 1 heating and 1 cooling sequence. 1 internal
temperature sensor, 1 outside temperature input, 1 auxiliary input for external temperature input, heat –
cool changeover or high/low limit.
The economizer controls an outdoor damper and optional fan. It activates the outdoor damper if there is
heating or cooling demand and if outdoor conditions are favorable for free heating or cooling. An additional
input may be used to close the damper based on an open contact input (for example high humidity or bad air
quality).
Flexible application configuration is made with a parameter-setting routine using the standard operation
terminal.
Name
- E
T
L
C
3
C
Ordering
Model
TLC3-ECO-230
TLC3-ECO-230-W01
TLC3-ECO-D-230
TLC3-ECO-D-230-W01
Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct),
SRA-Tn10 (room), SDB-Tn10-20 and AMI-S10 as immersion sensor.
Binary auxiliary devices (e.g. pumps, fans, on/off valves, etc): Do not directly connect devices that exceed specified
limits in technical specifications – observe startup current on inductive loads.
Doc: 70-00-0660, V1.1, Date: 20170322
Subject to alteration
Features
TLC3-ECO-D also includes
For 3-point or spring
return actuators
-
O
Voltage:
Housing
Control:
Series:
Item code
Variation
Standard
40-10 0214
Cooling only
40-10 0214-01
Deluxe
40-10 0215
Cooling only
40-10 0215-01
© Vector Controls GmbH, Switzerland
Compares outdoor temperature with indoor or control
temperature. Activates free heating or cooling.
Low power energy consumption: < 1W per unit
Relays switching for outputs each up to 300W
Optional external temperature control input
Choose between one 3-point actuator and 2 binary
outputs. (1 outdoor damper, 1 mechanical enable or fan.)
Password protected programmable user and control
parameters
Power cap protected real-time clock with 48hr power
backup
Time schedule events, with many options
Blue backlight
Infrared remote control receiver
With enable for
mechanical heating
or cooling or fan
Blank = 230V, 0 = 24V, 1 = 120V
Blank = square housing, U = 2x4" housing
ECO: Economizer
TLC3
Economizer with:
1 internal and 1 external temperature sensor
2 relay normally open outputs
TLC3-ECO Economizer
O
VERVIEW
Option
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Vector TLC3-ECO Series

  • Page 1 Cooling only 40-10 0215-01 Temperature sensors: Use Vector Controls NTC sensors to achieve maximum accuracy: SDB-Tn10-20 (duct), SRA-Tn10 (room), SDB-Tn10-20 and AMI-S10 as immersion sensor. Binary auxiliary devices (e.g. pumps, fans, on/off valves, etc): Do not directly connect devices that exceed specified limits in technical specifications –...
  • Page 2: Operation

    60 x 50 x 32 mm (2.4 x 2.0 x 1.26 in.) Distance for mounting screws: Horizontal and vertical: 45 to 63 mm (1.8 to 2.5 in.) Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3: Terminal Description

    With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too much. Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    Clock and time schedule settings retained for 48 hours (after powered for at least 10 hours). Error messages Err1: Error temperature sensor. The temperature sensor may be damaged or not present Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5: Clock Operation

    Repeat steps 4 and 5 for all 4 switching events. In case a switching event is not used, set its mode to “no”. Pr01 08:00 To review the entire schedule group, step through by repeatedly pressing the OPTION key from step 1 onwards to step 6. Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6: Setup And Configuration

    Press the POWER to leave the menu. The unit will return to normal operation if no button is pressed for more than 5 minutes. Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7: User Configuration

    Control temperature sensor is X2 and alternate sensor is internal temperature sensor If CP18 1: Control temperature sensor is internal sensor and alternate sensor is X2. Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 7 Subject to alteration...
  • Page 8: Control Configuration

    If the outdoor damper closed because the setpoint is reached, it will re-open after the indoor temperature decreased for the amount specified under hysteresis CP09. Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9: Output Configuration

    0 = No external input 1 = Alternative control input instead of internal sensor 2 = Close damper if contact is open (high humidity, low air quality) Doc: 70-00-0660, V1.1, Date: 20170322 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...