EAGLEHAWK CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
N, L
EARTH GROUND
SHORT-CIRCUITING!
USB 2.0
Device Interface
24V~0
24V~
EAGLEHAWK #1
1
2
24
V~
L
LINE
N
24 V~0
NOISE-FREE EARTH GROUND
Fig. 20. Incorrect polarity → SHORT-CIRCUITING!
Transformer Data
In Europe, if the EAGLEHAWK is powered by transformers,
then such transformers must be safety isolating transformers
conforming to IEC61558-2-6. In the U.S. and Canada, if the
EAGLEHAWK is powered by transformers, then such
transformers must be NEC Class-2 transformers.
Table 9. 1450 series transformers data
part #
primary side
1450 7287
-001
120 Vac
24 Vac, 50 VA
2 x 24 Vac, 40 VA, 100 VA from
-002
120 Vac
separate transformer
-003
120 Vac
24 Vac, 100 VA, 24 Vdc, 600 mA
-004
240/220 Vac 24 Vac, 50 VA
2 x 24 Vac, 40 VA, 100 VA from
-005
240/220 Vac
separate transformer
-006
240/220 Vac 24 Vac, 100 VA, 24 Vdc, 600 mA
Table 10. Overview of CRT Series AC/DC current
transformer
primary side
CRT 2
230 Vac
CRT 6
230 Vac
CRT 12
230 Vac
PRIMARY SIDE
230 VAC
24 VAC
24 V0
120 VAC
NOT
RECOMMENDED
Fig. 21. Connection of EAGLEHAWK controller
EN1Z-1005GE51 R0216
PC 1
PC 2
CPU 2
24V~0
24V~
EAGLEHAWK #2
1
2
REVERSED
!
POLARITY!
(ONLY ONE PER SYSTEM)
secondary side
max. AC
max. DC
current
current
2 A
500 mA
6 A
1300 mA
12 A
2500 mA
EAGLEHAWK
2
1

RIN-APU24

The RIN-APU24 Uninterruptable Power Supply can be
directly wired to an EAGLEHAWK controller.
See RIN-APU24 Uninterruptable Power Supply – Mounting
Instructions (EN0B-0382GE51) for a detailed wiring diagram.
Powering Panel Bus I/O Modules and Field Devices
The EAGLEHAWK, Panel Bus I/O modules, and field devices
can be powered by either separate transformers (see Fig. 22,
and Fig. 23) or by the same transformer.
NOTE: Use a min. distance of 10 cm between power cables
and 0...10 V / sensor cables in order to prevent
signal disturbances on the 0...10 V / sensor cables.
See also section "Cable Specifications" on page 18.
Powering Field Devices and Panel Bus I/O Module via Separate
Transformers
 24 V actuator connected to, e.g., an analog output module
 Field device located 100 ... 400 m from the analog output
module
F1
CLIOP822A
24 VAC
73
230 VAC
74
1...8
24 V0
11...18
Fig. 22. Power supply via a separate transformer
Powering Field Devices via Panel Bus I/O Module
 24 V actuator connected to, e.g., an analog output module
 Field device located max. 100 m from the analog output
module
F2
F1
CLIOP822A
24 VAC
73
230 VAC
74
1...8
24 V0
11...18
Fig. 23. Power supply via Panel Bus I/O Module

Lightning Protection

Please contact your local Honeywell representative for
information on lightning protection.
12
24 V0
230 VAC
24 VAC
F2
24 VAC
Y (0...10 Vdc)
GND
max. 400 m
24 VAC
Y (0...10 Vdc)
GND
max. 100 m