APPLICATION FIELD WIRING

REMOTE SENSING OF SAFETY LOCKOUT
The SAFETY SWITCH in the 530SE CONTROL BOX is equipped with a contact allowing remote sensing of burner
lockout. The electrical connection is made at terminal 4 (
Should lockout occur the 530SE CONTROL BOX will supply a power source of 120Vac to the connection terminal.
The maximum allowable current draw on this terminal (4) is 1 Amp.
WARNING:
If a neutral or ground lead is attached to this terminal, the CONTROL BOX on the burner will be damaged
should lockout occur.