Lennox CB26UH Series Installation Instructions Manual page 15

Hide thumbs Also See for CB26UH Series:
Table of Contents

Advertisement

NOTE - Refer to outdoor unit installation instructions for
system
start-up
instructions
and refrigerant
charging
instructions.
PRE-START-UP
CHECKS
Is the air handler properly and securely installed?
If horizontally configured, is the unit sloped up to 1/4
inch toward drain lines?
Will the unit be accessible for servicing?
Has an auxiliary pan been provided under the unit with
separate
drain for units installed above a finished
ceiling
or in any
installation
where
condensate
overflow could cause damage?
Have ALL unused
drain pan ports been properly
plugged?
Has the condensate
line been properly sized, run,
trapped, pitched, and tested?
Is the duct system correctly sized, run, sealed, and
insulated?
Have all cabinet openings and wiring been sealed?
Is the indoor coil factory-installed
TXV properly sized
for the outdoor unit being used?
Have all unused parts and packaging been disposed
of.'?
Is the filter clean, in place, and of adequate size?
Is the wiring neat, correct, and in accordance with the
wiring diagram?
Is the unit properly grounded and protected (fused)?
Is the thermostat
correctly
wired
and in a good
location?
Are all access panels in place and secure?
CHECK BLOWER OPERATION
Set thermostat to FAN ON,
The indoor blower should come on.
CHECK COOLING OPERATION
Set
thermostat
to
force
a
call
for
cooling
(approximately
5°F lower than the indoor ambient
temperature).
The outdoor unit should come on immediately and the
indoor blower should start between 30 - 60 seconds
later.
Check the airflow from a register to confirm that the
system is moving cooled air.
Set the
thermostat
5°F higher than
the
indoor
temperature.
The indoor blower and outdoor
unit
should cycle off.
CHECK ELECTRIC
HEATER (IF USED)
Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature).
The indoor blower
and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.
Set the thermostat so that it does not call for heat,
Allow up to 5 minutes for all sequencers to cycle off,
COOLING (COOLING
ONLY OR HEAT PUMP)
When the thermostat calls for cooling, 24 volts is put on the
blower time-delay
relay coil. After a delay, the indoor
blower relay energizes. The normally open contacts close,
causing the indoor blower motor to operate. The circuit
between R and Y is completed, closing the circuit to the
contactor in the outdoor unit, starting the compressor and
outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing
valve, switching the valve to the cooling position. (The
reversing
valve
remains
energized
as
long as the
thermostat selector switch is in the COOL position.)
At the completion
of the cooling demand and after the
relay's time-delay, the compressor and outdoor fan will
cycle off.
HEATING (ELECTRIC HEAT ONLY)
When the thermostat calls for heat, the circuit between R
and W is completed, and the heat sequencer is energized.
A time delay follows before the heating elements and the
indoor blower motor come on. Units with a second heat
sequencer can be connected with the first sequencer to W
on the thermostat subbase, or they may also be connected
to a second stage on the subbase.
HEATING (HEAT PUMP)
When the thermostat calls for heating, 24 volts is put on the
blower time-delay
relay coil. After a delay, the normally
open contacts close, causing the indoor blower motor to
operate. The circuit between R and Y is completed, closing
the circuit to the contactor in the outdoor unit, starting the
compressor
and outdoor fan motor.
Circuit R and G
energizes the blower relay, starting the indoor blower
motor.
If the room temperature should continue to fall, the circuit
between R and W1 is completed by the second-stage heat
room
thermostat.
Circuit
R-W1
energizes
a heat
sequencer.
The
completed
circuit
will
energize
supplemental
electric heat (if applicable).
Units with a
second heat sequencer can be connected with the first
sequencer to W1 on the thermostat. They may also be
connected to a second heating stage W2 on the thermostat
subbase.
TIME DELAY RELAY
On early production
units,
the indoor
blower
relay
energizes
after a 30 second
delay
and it remains
energized
for 30 seconds
after the call is satisfied.
The indoor blower
will remain
on for approximately
30 seconds
before
cycling
off.
In January
2006, the blower
relay was changed
to 1
second
delay ON and "45" second
delay OFF.
EMERGENCY
HEAT (HEATING HEAT PUMP)
If the selector switch on the thermostat
is set to the
emergency heat position, the heat pump will be locked out
of the heating circuit, and all heating will be electric heat (if
applicable), A jumper should be placed between W2 and E
Page15
CB(X)26UH
SERIES

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cbx26uh seriesCb26uh-r seriesCbx26uh-r series

Table of Contents