Wired Remote Controller Installation Method - LG PRCKD21E Installation Manual

Air conditioner
Table of Contents

Advertisement

Wired remote controller in-
stallation method
- Connect remote controller cable to the wired
remote controller installation plate as in the
following figure.
1
2
3
4
h The remote controller cable shall be pur-
chased separately by the site.
- After fixing cable in the guiding groove, at-
tach the wired remote controller installation
plate in the desired location.
h Before fixing the remote controller cable in
the guiding groove, install after removing
the closed part of the case in the direction
to install.
Guiding
groove
<Wired remote controller
installation plate front side>
- After placing the wired remote controller in-
stallation plate in the place you want to in-
stall the remote controller, firmly fix using
the fixing bolts. (If there is a reclamation box,
install the wired remote controller installation
plate according to the reclamation box.)
Top
Fix the remote
controller cable to
the guiding groove.
Use the fixing bolts
to firmly fix it on the wall.
Wired remote controller
Bottom
installation plate
12 V
GND
BUS_B
BUS_A
Remote
controller
cable
<Wired remote controller
installation plate back side>
Wall
After fixing the top parts of the remote con-
troller to the wired remote controller installa-
tion plate as in the figure, push the bottom
part to combine the remote controller and the
wired remote controller installation plate.
If remote controller is separated from remote
controller installation plate, use the driver to
insert in the arrow hole as in the right side fig-
ure, and if you pull toward front direction, the
remote controller is separated.
<Combining order>
Wall
<Separation order>
Wall
Use the extension cable to connect CON-
TROL KIT and remote controller.
Purchase and use the extension cable at the
site.
Please contact the specialty store(Hisys) for
purchase of extension cable.
During the connection of the cable, com-
ply with the following.
- During the installation of the extension
cable, check the connection direction of
remote controller side and CONTROL
KIT before the installation.
- If the extension cable is reversely con-
nected, the product will not operate.
- Extension cable specification: use 2547
1007 22# 2core 4shield, 5Ø or equiva-
lent level or higher
TEST OPERATION
47
Wall
Wall
601
602
603
604
12V
GND
BUS_B
BUS_A
CONTROL KIT inside