NVB Series B-Vent Gas Fireplace

EB-1 Electrical Box

The fireplace, when installed, must be elec-
trically connected and grounded in accor-
dance with local codes or, in the absence
of local codes, with the current CSA C22.1
Canadian Electrical Code.
For USA installations, follow local codes
and the National Electrical Code, ANSI/
NFPA No. 70.
It is strongly suggested that the wiring of
the EB-1 electrical junction box be carried
out by a licensed electrician.
Ensure that the power to the supply line
has been disconnected before commenc-
ing this procedure.
Once the fireplace is secured, complete wiring
the fan kit. Remove knockout in the center of the back
of the EB1 and install listed cable clamps. Feed electri-
cal wire through cable clamp leaving approximately six
(6) inches of wire exposed through the EB1. Secure
cable clamp to the wire.
Attach white wire from power source to one (1) wire of
receptacle and secure with a nut. Attach black wire from
power source to the other wire of the receptacle and
secure with a nut. Be sure nuts are tightened securely.
Secure the EB1 assembly to the inside of the electrical
box coverplate using two (2) screws. Attach the cover
to the face of the EB1 while being careful to position
excess wire completely within the EB1. Attach the cov-
erplate to the fireplace. (Fig. 11)
Inside
Outside
Fig. 11 Junction box (EB-1) hook-up.
10
Electrical Box
FP580
FP580
INSTA VENT FREE
EB1 JUNCTION BOX
11/18/97
Install the Venting System,
Flashing and Termination
See venting installation instructions provided by the B-
Vent manufacturer.
Refer to Pages 4-5, Figures 1-4 to locate chimney cen-
terline dimension from a combustible back wall.
Minimum vertical chimney height — 12 feet (3.65 m).
Maximum vertical height — 40 feet (12 m).
Minimum height with two 90° elbows — 16 feet
(4.06m)
Elbow requirements allow a maximum of two 90°
elbows or four 45 degree elbows per installation.
(Two 45 degree elbows = One 90° elbow.) See
venting chart for proper elbow offset runs. Use
Table 4 for NVB36/42 installations when not in-
stalling the GSKBB Single Panel Glass Door. Use
Table 5 for NVB36/42 installations when install-
ing the GSKBB Single Panel Glass Door.
For firestop positioning, refer to Figure 12. Only one
(1) firestop required per frame. NOTE: A firestop is not
required at the roof.
Attic Installation
Firestop position when area above ceilign is an attic.
Ceiling Installation
Firestop position when are above ceiling is NOT an attic.
Fig. 12 Firestop/draftstop positions.
FP384
FIRESTOP
11/21/96
adapted from IGF53
Nails (4)
Firestop Spacer
Joist
(Firestop/draftstop
appearances may vary.
Only one (1) firestop
required per frame.)