Troubleshooting - Majestic fireplaces 33LDVR Installation Instructions And Homeowner's Manual

Builder rear vent direct vent
Table of Contents

Advertisement

START
Gas Supply On
Pilot Lights With Piezo
Ignitor
Pilot Stays Lit
Pilot Lights Main Burner
SYSTEM OK
10007317
Troubleshooting - Honeywell Millivolt Valve
Remove Window Frame Assembly Before Service Work
YES
YES
YES
YES
LDVR Series Direct Vent Gas Fireplace
CHECK
Supply Line Hooked Up
NO
Shutoff Valve Open
Lockout Has Engaged. Wait 60
Seconds And Try Again.
For Spark At Electrode While
Depressing Piezo
NO
1/8" Gap To Pilot Hood Needed.
All Wiring Connections
Replace Piezo Ignitor
For Air In The Lines
Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
All Wiring Connections
NO
Replace Thermopile
Thermocouple Needs A Min. Of
14mv
Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.
Valve Is Turned On
Wall Switch Is Not Turned On.
Watch For Grounded Wires!
NO
Thermopile Needs A Min. 325mv.
Plugged Burner Orifice
29