Installer Mode - Rheem RTGH-RH11DV Use And Care Manual

Condensing tankless water heater
Hide thumbs Also See for RTGH-RH11DV:
Table of Contents

Advertisement

▪ G. INSTALLER MODE
Installer Mode will activate when button
Index
Default
N/A
1:EH
2:CE
3:FC
GA
00
4:FH
00
5:FL
6:RC
oFF
7:RM
Itnl
8:RT
HI-2
9:HT
HI-2
6
10:IV
0 - 2
11:HA
is pressed and held for five seconds while the water heater display is powered Off.
Figure 38– Installer Mode Screens
Parameter
Error History
Clear Error & System
initialize
Unit
Maximum Fan Speed
Minimum Fan Speed
Recirculation Pump
Operation
Recirculation Mode
Recirculation Temperature
Hot Water Temperature
Prevent Ignition
This water heater may be installed at elevations up to 10,000 feet and operate on either
High Elevation Mode
NOTE: Use a combustion analyzer to ensure CO and
(negative) directions (approximately 1/8 turn) if the measured
Allows the Installer to View the Unit Error History
Range: E0:XX – E9:XX
PPHr : Pump Running Time
Use to choose unit (Water flow rate, Temperature)
LIt ℃ : Liter/minute, Celsius
GAL °F : Gallon/minute, Fahrenheit
Adjusts Maximum Fan Speed
Adjusts Minimum Fan Speed
Turns the Recirculation Pump On and Off
Range: On – Pump On, oFF – Pump Off
NOTE: 6:RC must be set to On to select 7:RM
Sets the Recirculation Mode
Range: ItnL – Internal Recirculation
EtnL – External Recirculation / On Demand Kit,
tt24 – Tilte 24 Mode, bYPS-Cross over
Sets Recirculation Temperature
Range: LO – Low Temperature, HI-1 – Middle Temperature,
HI-2 – High Temperature
Sets Hot Water Temperature
Range: LO – Low Temperature, HI-1 – Middle Temperature,
HI-2 – High Temperature
Temporarily disables the water heater from igniting for a set period of time.
Range: 0 – 20 Minutes
Natural or LP. The appliance will de-rate by 4% for each 1,000 feet above sea level.
Select the appropriate installation location as described below.
Selects Installation Location for Proper Water Heater Operation at Altitude:
0-2 for installation locations from sea level to 2,000 feet
2-5 for locations from 2,000 to 5,000 feet
5-8 for locations from 5,000 to 8,000 feet
this manual. Adjust the offset screw in the clockwise (positive) or counterclockwise
Description
EHIS :Error History
rH : Burn Hour
bnCY : Burn Cycle
In: System initialize
Range: -30 - +30
Range: -30 -+30
Default: 0 – 2
CO
are within the ranges shown in
2
CO
is out of range.
AP18733 REV. 3.2.17
61
value on LOW FIRE
2