Download Print this page

Siemens SIMATIC NET IE RJ45 Plug PRO Assembly Instructions Manual page 5

Advertisement

Available languages

Available languages

Montageanleitung für / Assembly Instructions for IE RJ45 Plug PRO (6GK1901-1BB10-6AA0)
a
Forcing nut
b
Sealing ring
c
Rear wall
d
Latch
e
Contact holder
f
Housing
g
Metal foil
5. Take the stripping tool in your right hand.
6. Place the cable on the shortest stripping
setting (approx. 30 mm). Use your left
index finger as the limit stop.
10. Pull of the cable jacket, shield and the
white filler with your hand.
Copyright © 2010 Siemens AG
1. Release the forcing nut (a) and sealing
ring (b) from the rear wall (c) of the plug.
2. Push the forcing nut (a), the sealing ring
(b) and the back wall (c) loosely over the
cable.
7. Fit the cable in the stripping tool. Your left
index finger is the limit stop.
8. Tighten the stripping tool.
11. Turn back the braid over the cable jacket
and secure it with the supplied metallic
cable foil.
12. Remove the exposed foil shield and white
filler below it.
3. Use the yellow knife cassette
6GK1901-1GB00 (12 mm knife clearance)
in the stripping tool!
4. When necessary, adjust the cutting depth
of the knife cassette with the socket-head
screws at the head end of the tool!
9. To strip the insulation, turn the tool in the
direction of the arrow
- approx. 4 times for PVC insulation
- approx. 8 times for PUR insulation.
13. Arrange the wires according their colors
as shown in the figure above.
14. Cut the wires to a length of 15 mm.