Carrier WeatherMaker 50KCQ A04 Series Service And Maintenance Instructions page 67

Single package rooftop unit
Hide thumbs Also See for WeatherMaker 50KCQ A04 Series:
Table of Contents

Advertisement

MOTOR/DRIVE
UNIT
COMBO
Medium static
3 phase
04
High static
Medium static
3 phase
05
High static
Medium static
3 phase
06
High static
= factory setting
NOTES:
1. Do not adjust pulley further than 5 turns open.
2. Do not set motor pulley above 5 turns open for A or AX section belts.
3. Do not set motor pulley below 1 turn open for B or BX section belts.
APPENDIX C — FAN PERFORMANCE
Table O — Fan RPM at Motor Pulley Settings
0
0.5
1
1251
1208
1165
1466
1423
1380
1303
1265
1226
1466
1423
1380
1380
1349
1317
1550
1516
1482
67
MOTOR PULLEY TURNS OPEN
1.5
2
2.5
3
1121
1078
1035
992
1337
1294
1251
1207
1188
1150
1112
1073
1337
1294
1251
1207
1286
1254
1223
1192
1447
1413
1379
1345
3.5
4
4.5
5
949
905
862
819
1164
1121
1078
1035
1035
997
958
920
1164
1121
1078
1035
1160
1129
1097
1066
1311
1276
1242
1208