Carrier WeatherMaker 50KCQ A04 Series Service And Maintenance Instructions page 39

Single package rooftop unit
Hide thumbs Also See for WeatherMaker 50KCQ A04 Series:
Table of Contents

Advertisement

19
LED ON
18
D
17
LED ON
LED OFF
16
15
14
LED OFF
13
12
11
10
9
50
40
45
55
60
DEGREES FAHRENHEIT
Fig. 60 — Outside Air Temperature Changeover
Set Points
30
25
20
15
10
5
0
0.13
0.20 0.22
STATIC PRESSURE (in. wg)
Fig. 61 — Outdoor-Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control, the standard outdoor dry bulb
sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory
sensor must be mounted in the return airstream. (See Fig. 62.)
Wiring is provided in the EconoMi$er IV wiring harness.
ECONOMI$ER IV
Fig. 62 — Return-Air Temperature or Enthalpy
Sensor Mounting Location
In this mode of operation, the outdoor-air temperature is com-
pared to the return-air temperature and the lower temperature
airstream is used for cooling. When using this mode of
C
LED ON
B
LED ON
LED OFF
A
LED OFF
70
75
90
65
80
85
0.25
0.30 0.35 0.40
0.45
ECONOMI$ER IV
CONTROLLER
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
changeover control, turn the enthalpy set point potentiometer
fully clockwise to the D setting. (See Fig. 59.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry
bulb temperature sensor with the accessory enthalpy sensor in
the same mounting location. (See Fig. 62.) When the outdoor
air enthalpy rises above the outdoor enthalpy changeover set
point, the outdoor-air damper moves to its minimum position.
The outdoor enthalpy changeover set point is set with the out-
door enthalpy set point potentiometer on the EconoMi$er IV
controller. The set points are A, B, C, and D. (See Fig. 63.) The
factory-installed 620-ohm jumper must be in place across ter-
minals SR and SR+ on the EconoMi$er IV controller.
100
95
CONTROL
CONTROL POINT
CURVE
APPROX. deg. F (deg. C)
AT 50% RH
A
73 (23)
B
70 (21)
C
67 (19)
D
63 (17)
0.50
35
(2)
35
(2)
Fig. 63 — Enthalpy Changeover Set Points
N1
N
P1
P
T1
T
AQ1
AQ
SO+
SO
SR+
SR
Fig. 64 — EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV controller
uses two enthalpy sensors (HH57AC078 and CRENT-
DIF004A00), one in the outside air and one in the return air
39
85
90
(29)
(32)
80
(27)
75
(24)
70
(21)
65
(18)
60
(16)
A
55
(13)
B
50
C
(10)
45
D
(7)
40
(4)
A
B
C
D
40
45
50
55
60
65
70
75
80
85
90
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
(27)
(29)
(32)
EXH
Set
2V
10V
EXH
Min
Pos
Open
DCV
Max
2V
10V
DCV
DCV
Set
2V
10V
Free
Cool
B
C
D
A
95
100
105
110
(35)
(38)
(41)
(43)
HIGH LIMIT
CURVE
95
100
105
110
(35)
(38)
(41)
(43)
TR1
TR
24
24 Vac
Vac
COM
HOT
_
+
1
2
5
4
3
EF1
EF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents