Dometic CD Series Installation And Operating Manual page 15

Drawer
Hide thumbs Also See for CD Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
CD20, CD30
Compressor does not run
Feature
 0 Volt
U
Term
 U
U
Term
ON
During attempted start
 U
up U
Term
OFF
During attempted start
 U
up U
Term
ON
Electric circuit between
the pins in the
compressor interrupted
U
Voltage between the positive and negative electronic terminals
Term
U
Switch on voltage of the electronic connection terminals
ON
(see chapter "Technical description" on page 10)
U
Switch off voltage of the electronic connection terminals
OFF
(see chapter "Technical description" on page 10)
EN
Possible cause
There is an interruption in the
connection between the battery and
the electronics
Main switch faulty (if installed)
Additional supply line fuse has blown
(if installed)
Battery voltage is too low
Loose cable connection
Poor contact (corrosion)
Cable cross section too small
Battery capacity too low
Ambient temperature too high
Insufficient ventilation and/or air
supply
Condensor is dirty
Defective compressor
Troubleshooting
Remedy
Establish a connection
Replace the main switch
Replace the supply line
fuse
Charge the battery
Establish a connection
Replace the cable
(fig. 6, page 5)
Replace the battery
Move the refrigerator to
another location
Clean the condenser
Replace the compressor
15