Outdoor Fan Motor Control - Toshiba RAS-18J2KVSG-E Service Manual

Indoor/outdoor unit, r32 inverter
Hide thumbs Also See for RAS-18J2KVSG-E:
Table of Contents

Advertisement

Item
3. Outdoor fan
The blowing air volume at the outdoor unit side is controlled.
motor control
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
Air conditioner ON
(Remote controller)
Indoor unit controller
1) Outdoor unit
operation command
(Outdoor fan control)
2) Fan speed ≥ 400.
when the motor OFF.
(by strong wind)
Fan motor ON
3) Fan lock
4) Motor operates as shown in the table below.
In cooling operation
Compressor speed
RAS-18J2AVSG-E
RAS-22J2AVSG-E
RAS-24J2AVSG-E
Fan speed range
To ≥ 38°C
To ≥ 28°C
To ≥ 15°C
To
To ≥ 5.5°C
To ≥ 0°C
To ≥ 0°C
When To is abnormal
Outdoor Fan Speeds (rpm)
Model name
f0
RAS-18J2AVSG-E
0
RAS-22J2AVSG-E
0
0
RAS-24J2AVSG-E
Operation flow and applicable data, etc.
Fan motor OFF continues
YES
(Use wind for heat
NO
YES
Air conditioner
NO
30.6 ≤ Hz
Hz < 20.4
20.4 ≤ Hz < 30.6
30.6 ≤ Hz
Hz < 20.5
20.4 ≤ Hz < 30.7
32.4 ≤ Hz
Hz < 20.4
20.4 ≤ Hz < 32.4
MIN
MAX
MIN
MAX
MIN
f6
fB
f8
fE
fA
f5
fA
f7
fE
f9
f3
f7
f5
f9
f7
f2
f5
f4
f7
f6
f1
f3
f3
f5
f4
f1
f2
f2
f4
f3
OFF
fB
OFF
fE
f1
f1
f2
f3
f4
300
300
300
360
450
300
300
300
360
450
300
300
300
450
500
exchanging)
Alarm
OFF
display
Compressor speed
RAS-18J2AVSG-E
RAS-22J2AVSG-E
RAS-24J2AVSG-E
MAX
Fan speed range
fE
To ≥ 10°C
fE
To ≥ 5°C
fB
To
To ≥ -3°C
f9
To ≥ -10°C
f7
To < - 10°C
f5
When To is abnormal
fE
Fan speed range
f5
f6
f7
f8
f9
500
550
600
650
500
550
600
650
600
650
650
700
- 38 -
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
In heating operation
Hz < 20.4
20.4 ≤ Hz < 48.6
Hz < 20.5
20.4 ≤ Hz < 48.7
Hz < 20.6
20.4 ≤ Hz < 43.8
MIN
MAX
MIN
MAX
f7
f8
f9
fB
fE
fE
fE
fE
fE
fE
fE
fF
fA
fB
fC
fD
fE
700
800
900
900
900
700
800
900
950
950
750
800
900
900
900
48.6 ≤ Hz
48.6 ≤ Hz
43.8 ≤ Hz
MIN
MAX
f9
fE
fE
fE
fE
fF
fF
900
950
950