Planning
4
Acoustic and optical configuration
4.5.4 DBS728 optical signals
No.
Flash type
0
Flash
1
Flash
2
Flash
3
Flash
4
Flash
5
Flash
6
Flash
7
Reserve
30 | 56
Building Technologies
Fire Safety
Pulse pattern
Flashing
frequency
0.5 Hz
4.5 ms
2 s
0.5 Hz
4.5 ms
2 s
0.5 Hz
4.5 ms
2 s
0.5 Hz
4.5 ms
2 s
0.5 Hz
20 ms
2 s
0.5 Hz
20 ms
2 s
0.5 Hz
20 ms
2 s
—
—
Supervision function: The LEDs are activated once approx. every 4.5 hours.
1
Luminous intensity at
32 V,
angle-dependent (typ.)
Dark/low
Dark/low
Dark/low
Dark/low
Light/high
Light/high
Light/high
—
Standard / Notes
—
Monitoring function
1
Parameter is not
visible in the
'Cerberus-
Engineering-Tool'
Listed as a duplicate
of parameter '0' for
backward
compatibility
Parameter is not
visible in the
'Cerberus-
Engineering-Tool'
Listed as a duplicate
of parameter '0' for
backward
compatibility
—
Monitoring function
1
Parameter is not
visible in the
'Cerberus-
Engineering-Tool'
Listed as a duplicate
of parameter '4' for
backward
compatibility
—
A6V10320094_m_en_--
2017-10-31