Dbs728 Acoustic Signals - Siemens DBS721 Technical Manual

Sounder interbase, sounder beacon interbase, sounder interbase with supplementary optical indication
Hide thumbs Also See for DBS721:
Table of Contents

Advertisement

Planning
4
Acoustic and optical configuration

4.5.3 DBS728 acoustic signals

No.
Tone
Frequency pattern
Sweep from
1
Continuous
970 Hz
2
Intermittent
950 Hz
3
Sweep-down 1200 Hz
4
Slow-whoop
500 Hz
Sweep-up,
linear
5
Pulse tone
500 Hz
6
Intermittent
500 Hz
7
Continuous
500 Hz
8
Alternating
560 Hz
440 Hz
9
Intermittent
420 Hz
10
Slow-whoop
500 Hz
Sweep-up,
linear
28 | 56
Building Technologies
Fire Safety
Pulse pattern
to
0
1 s
0
1 s
500 Hz
0
1200 Hz
3.5 s
0
0.5 s
0.15 s
0
0.1 s
0.15 s
0
0.6 s
0
0.1 s
0
0.4 s
0.6 s
0
0.65 s
1200 Hz
3.75 s
0
0.25 s
Standards
Adjustable max.
sound levels with
blanking plate (typ.
values in [dBA/1m]
)
1
at 12 V
at 32 V
89
93
'evacuate'
BS 5839 Part 1 1988,
EN 54-3
90
93
'alert'
BS 5839 Part 1 1988,
EN 54-3
88
91
DIN tone
DIN 33404 Part 3,
EN 54-3
88
90
NEN 2575
(Netherlands)
EN 54-3
86
89
Swedish Standard
SS 03 17 11, No. 1
'Imminent Danger',
EN 54-3
86
89
Swedish Standard
SS 03 17 11, No. 6
'Local Warning',
EN 54-3
86
89
Swedish Standard
SS 03 17 11, No. 4
'All clear',
EN 54-3
86
88
'French fire sound'
NF S 32-001 -1975,
EN 54-3
85
87
Australia 'Alert'
AS 2220 -1978,
EN 54-3
88
91
Australia 'Action'
AS 2220 -1978,
EN 54-3
A6V10320094_m_en_--